Analog Input Modules for
Compact FieldPoint and FieldPoint
Specifications
(contintued)
Input Range
Module
[c]FP-AI-100
Input Range
Voltage
Nominal
0 to 1 V
0 to 5 V
0 to 15 V
0 to 30 V
±1 V
±5 V
±15 V
±30 V
0 to 20 mA
4 to 20 mA
±20 mA
0 to 20 V
0 to 60 V
0 to 120 V
±20 V
±60 V
±120 V
0 to 1 V
0 to 5 V
0 to 10 V
±60 mV
±300 mV
±1 V
±5 V
±10 V
0 to 20 mA
4 to 20 mA
±20 mA
With
Overranging
0 to 1.2 V
0 to 6 V
0 to 18 V
0 to 36 V
±1.2 V
±6 V
±18 V
±36 V
0 to 24 mA
3.5 to 24 mA
±24 mA
0 to 1.04 V
0 to 5.2 V
0 to 10.4 V
±65 mV
±325 mV
±1.04 V
±5.2 V
±10.4 V
0 to 21 mA
3.5 to 21 mA
±21 mA
Effective
Effective
Resolution
Resolution
1.5 mV
5 mV
15 mV
25 mV
1.5 mV
5 mV
25 mV
40 mV
15 µA
15 µA
20 µA
15 mV
40 mV
70 mV
25 mV
70 mV
125 mV
25 µV
90 µV
190 µV
3 µV
16 µV
40 µV
190 µV
380 µV
500 nA
500 nA
700 nA
Typical
15 to 35 °C
1.5 mV
6 mV
15 mV
30 mV
2 mV
10 mV
30 mV
60 mV
20 µA
20 µA
40 µA
20 mV
50 mV
100 mV
40 mV
120 mV
220 mV
50 µV
180 µV
300 µV
30 µV
40 µV
75 µV
300 µV
650 µV
1 µA
1 µA
1 µA
Offset Error
Maximum
–40 to 70 °C
15 mV
27 mV
45 mV
70 mV
20 mV
40 mV
90 mV
160 mV
45 µA
45 µA
110 µA
100 mV
150 mV
250 mV
175 mV
350 mV
700 mV
650 µV
1500 µV
2500 µV
500 µV
600 µV
850 µV
2500 µV
4000 µV
10 µA
10 µA
10 µA
Gain Error
Typical
15 to 35 °C
0.09%
0.09%
0.12%
0.22%
0.08%
0.08%
0.11%
0.20%
0.09%
0.09%
0.06%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.03%
0.03%
0.03%
0.03%
0.03%
0.03%
0.03%
0.03%
0.04%
0.04%
0.04%
Maximum
–40 to 70 °C
0.50%
0.50%
0.55%
0.55%
0.50%
0.55%
0.60%
0.55%
0.51%
0.51%
0.55%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.2%
0.2%
0.2%
Current
[c]FP-AI-102
Voltage
[c]FP-AI-110
Voltage
Current
Isolation Voltage
Maximum isolation voltage ............................. 250 V
rms
, Installation Category II
Channel-to-channel isolation ........................... No isolation between channels
Transient overvoltage....................................... 2,300 V
rms
Safety
This product is designed to meet the requirements of the following standards of safety for electrical
equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to the product label or to
ni.com
Physical Characteristics
LED indicators
POWER (green) ..........................................
READY (green) ...........................................
Dimensions (including terminal base)..............
Weight
[c]FP-AI-110, [c]FP-AI-111 ..........................
[c]FP-AI-100, [c]FP-AI-102 ..........................
Power on and self-test passed
Module configured and ready
10.9 by 10.9 by 9.1 cm (4.3 by 4.3 by 3.6 in.)
136 g (4.8 oz)
145 g (5.1 oz)
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions.......................................................... EN 55011 Class A at 10 m FCC Part 15A above 1 GHz
Immunity........................................................... EN 61326:1997 + A2:2001, Table 1
For EMC compliance, operate this device with shielded cabling.
Power Requirement
Power from network module
[c]FP-AI-110, [c]FP-AI-111 .......................... 350 mW
[c]FP-AI-100, [c]FP-AI-102 .......................... 400 mW
CE Compliance
This product meets the essential requirements of applicable European Directives, as amended for
CE Marking, as follows:
Low-Voltage Directive (safety)......................... 73/23/EEC
Electromagnetic Compatibility
Directive (EMC).......................................... 89/336/EEC
Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance
information. To obtain the DoC for this product, visit
ni.com/hardref.nsf/
and search by model number
or product line.
Environment
Operating temperature..................................... -40 to 70 °C
Storage temperature ........................................ -55 to 85 °C
Relative Humidity ............................................. 10 to 90%, noncondensing
Shock and Vibration
These specifications apply only to Compact FieldPoint. NI recommends Compact FieldPoint if your
application is subject to shock and vibration.
Operating vibration, random
(IEC 60068-2-64) ........................................ 10 to 500 Hz, 5 g
rms
Operating vibration, sinusoidal
(IEC 60068-2-6) .......................................... 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27) ........................................ 50 g, 3 ms half sine, 18 shocks at 6 orientations;
30 g, 11 ms half sine, 18 shocks at 6 orientations
Module
[c]FP-AI-100, [c]FP-AI-102
[c]FP-AI-110
Filter Settings
50 Hz
60 Hz
500 Hz
50 Hz
60 Hz
500 Hz
Update Rate
(All Channels)
2.8 ms
1.470 s
1.230 s
0.173 s
1.230 s
1.050 s
0.290 s
Input Bandwidth
(–3 dB)
170 Hz
13 Hz
16 Hz
130 Hz
13 Hz
16 Hz
130 Hz
[c]FP-AI-111
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • info@ni.com • ni.com