LabVIEW Real-Time
Controller Interfaces with Ethernet
Specifications
Network
Environmental
Network interface ............................................ 10BaseT and 100BaseTX Ethernet
FieldPoint modules are intended for indoor use only. For outdoor use, they must be installed in a
Compatibility .................................................... IEEE 802.3
suitable sealed enclosure.
Communication rates ....................................... 10 Mb/s, 100 Mb/s, autonegotiated
Maximum cabling distance.............................. 100 m/segment
Maximum power to connected I/O modules... 9 W
Operating temperature..................................... -25 to 60 °C
Storage temperature........................................ -55 to 85 °C
Relative humidity ............................................. 10 to 90%, noncondensing
Maximum altitude............................................ 2,000 m; at higher altitudes the isolation voltage
ratings must be lowered
Maximum number of banks ............................. Determined by network topology
Memory
Pollution Degree...............................................
2
cFP-2000........................................................... 32 MB nonvolatile; 16 MB DRAM
cFP-2010........................................................... 64 MB nonvolatile; 32 MB DRAM
cFP-2020........................................................... 64 MB nonvolatile; 32 MB DRAM
Shock and Vibration
Operating vibration
Random (IEC 60068-2-64).......................... 10–500 Hz, 5 grms
Sinusoidal (IEC 60068-2-6)........................ 10–500 Hz, 5 g
For information about the memory used by the LabVIEW RT module and the operating
system, go to ni.com/info and enter rdfpec.
Operating shock (IEC 60068-2-27).................... 50 g, 3 ms half sine, 18 shocks at 6 orientations;
30 g, 11 ms half sine, 18 shocks at 6 orientations.
Serial Ports
cFP-2000........................................................... One RS-232, DTE
cFP-2010........................................................... Two RS-232, DTE
cFP-2020........................................................... Three RS-232, DTE; one RS-485, DTE
Safety
This product is designed to meet the requirements of the following standards of safety for electrical
equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
RS-485 Isolation Voltage
Maximum isolation voltage ............................. 100 V
rms
Transient overvoltage....................................... 740 V
rms
For UL, hazardous location, and other safety certifications, refer to the product label or to ni.com.
Power Requirement
Power supply range.......................................... 11 to 30 VDC
Recommended power supply........................... PS-5
cFP-BP-4 system ........................................ 15 W
cFP-BP-8 system ........................................ 20 W
Power consumption
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions.......................................................... EN 55011 Class A at 10 m FCC Part 15A above 1 GHz
Immunity........................................................... EN 61326:1997 + A2:2002, Table 1
For EMC compliance, operate this device with shielded cabling.
cFP-2000 .................................................... 4.8 W + 1.1 (I/O module power requirements)
cFP-2010 .................................................... 5.0 W + 1.1 (I/O module power requirements)
cFP-2020 .................................................... 6.1 W + 1.1 (I/O module power requirements)
CE Compliance
This product meets the essential requirements of applicable European Directives, as amended
for CE Marking, as follows:
Low-Voltage Directive (safety)......................... 73/23/EEC
Electromagnetic Compatibility
Directive (EMC) ................................................ 89/336/EEC
Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance
information. To obtain the DoC for this product, click Declarations of Conformity visit ni.com/hardref.nsf/
and search by model number or product line.
Physical Characteristics
LED indicators
POWER (green) .......................................... Valid power to module
STATUS (red).............................................. Failure condition
LINK/ACTIVE (green) ................................. Valid network connection when lit;
Ethernet activity when blinking
100 Mbps (yellow)..................................... Ethernet speed (10 Mb/s if unlit)
User-defined .............................................. 3 bicolor, 1 green
DIP switches
cFP-2000, cFP-2010 ................................... 3 user-defined, 3 predefined
cFP-2020 .................................................... 3 user-defined, 5 predefined
External digital I/O (cFP-2020) ......................... 2 switch inputs, 2 (5 V) digital outputs
Screw-terminal wiring ..................................... 16-26 AWG copper conductor wire with 7 mm (0.28 in.)
of insulation stripped from the end
Torque for screw terminals.............................. 0.5-0.6 N m (4.4–5.3 lb in.)
Weight
Dimensions
cFP-2000.............................................. 286 g (10.1 oz)
cFP-2010.............................................. 293 g (10.3 oz)
cFP-2020.............................................. 326 g (11.5 oz)
cFP-20xx on cFP-BP-4 backplane........ 127 by 246 by 106 mm (5.0 by 9.7 by 4.2 in.)
cFP-20xx on cFP-BP-8 backplane........ 127 by 441 by 106 mm (5.0 by 17.4 by 4.2 in.)
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • info@ni.com • ni.com 521