LabVIEW Real-Time
Controller Interfaces with Ethernet
Compact FieldPoint Real-Time
Ethernet Controller Interfaces
Specifications
Network
Network interface ............................................
Compatibility ....................................................
Communication rates .......................................
Maximum cabling distance..............................
Maximum power to connected I/O modules ...
Maximum number of banks .............................
10BaseT and 100BaseTX Ethernet
IEEE 802.3
10 Mb/s, 100 Mb/s, autonegotiated
100 m/segment
9W
Determined by network topology
Environmental
FieldPoint modules are intended for indoor use only. For outdoor use, they must be installed in a
suitable sealed enclosure.
Operating temperature..................................... -25 to 60 °C
Storage temperature ........................................ -55 to 85 °C
Relative humidity ............................................. 10 to 90%, noncondensing
Maximum altitude ............................................ 2,000 m; at higher altitudes the isolation voltage
ratings must be lowered
Pollution Degree............................................... 2
Memory
cFP-2000 ........................................................... 32 MB nonvolatile; 16 MB DRAM
cFP-2010 ........................................................... 64 MB nonvolatile; 32 MB DRAM
cFP-2020 ........................................................... 64 MB nonvolatile; 32 MB DRAM
For information about the memory used by the LabVIEW RT module and the operating
system, go to
ni.com/info
and enter
rdfpec.
Shock and Vibration
Operating vibration
Random (IEC 60068-2-64).......................... 10–500 Hz, 5 g
rms
Sinusoidal (IEC 60068-2-6) ........................ 10–500 Hz, 5 g
Operating shock (IEC 60068-2-27).................... 50 g, 3 ms half sine, 18 shocks at 6 orientations;
30 g, 11 ms half sine, 18 shocks at 6 orientations.
Serial Ports
cFP-2000 ........................................................... One RS-232, DTE
cFP-2010 ........................................................... Two RS-232, DTE
cFP-2020 ........................................................... Three RS-232, DTE; one RS-485, DTE
Safety
This product is designed to meet the requirements of the following standards of safety for electrical
equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to the product label or to
ni.com.
RS-485 Isolation Voltage
Maximum isolation voltage ............................. 100 V
rms
Transient overvoltage....................................... 740 V
rms
Power Requirement
Power supply range..........................................
Recommended power supply...........................
cFP-BP-4 system ........................................
cFP-BP-8 system ........................................
Power consumption
cFP-2000 ....................................................
cFP-2010 ....................................................
cFP-2020 ....................................................
11 to 30 VDC
PS-5
15 W
20 W
4.8 W + 1.1 (I/O module power requirements)
5.0 W + 1.1 (I/O module power requirements)
6.1 W + 1.1 (I/O module power requirements)
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions.......................................................... EN 55011 Class A at 10 m FCC Part 15A above 1 GHz
Immunity........................................................... EN 61326:1997 + A2:2002, Table 1
For EMC compliance, operate this device with shielded cabling.
CE Compliance
This product meets the essential requirements of applicable European Directives, as amended
for CE Marking, as follows:
Low-Voltage Directive (safety)......................... 73/23/EEC
Electromagnetic Compatibility
Directive (EMC) ................................................ 89/336/EEC
Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance
information. To obtain the DoC for this product, click Declarations of Conformity visit
ni.com/hardref.nsf/
and search by model number or product line.
Physical Characteristics
LED indicators
POWER (green) .......................................... Valid power to module
STATUS (red).............................................. Failure condition
LINK/ACTIVE (green) ................................. Valid network connection when lit;
Ethernet activity when blinking
100 Mbps (yellow)..................................... Ethernet speed (10 Mb/s if unlit)
User-defined .............................................. 3 bicolor, 1 green
DIP switches
cFP-2000, cFP-2010 ................................... 3 user-defined, 3 predefined
cFP-2020 .................................................... 3 user-defined, 5 predefined
External digital I/O (cFP-2020) ......................... 2 switch inputs, 2 (5 V) digital outputs
Screw-terminal wiring ..................................... 16-26 AWG copper conductor wire with 7 mm (0.28 in.)
of insulation stripped from the end
Torque for screw terminals .............................. 0.5-0.6 N m (4.4–5.3 lb in.)
Weight
Dimensions
cFP-2000.............................................. 286 g (10.1 oz)
cFP-2010.............................................. 293 g (10.3 oz)
cFP-2020.............................................. 326 g (11.5 oz)
cFP-20xx on cFP-BP-4 backplane ........ 127 by 246 by 106 mm (5.0 by 9.7 by 4.2 in.)
cFP-20xx on cFP-BP-8 backplane ........ 127 by 441 by 106 mm (5.0 by 17.4 by 4.2 in.)
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • info@ni.com • ni.com