High-Speed Counter Modules for Compact FieldPoint
Physical Characteristics
LED indicators
POWER (green) ...............................
READY (green) ................................
Count inputs <0..7> (green) ................
Gate inputs <0..3> (green) ..................
Outputs <0..3> (green) ........................
Dimensions (including terminal base)
Power on and self-test passed
Module configured and ready
On/off state of counter input
On/off state of gate input
On/off state of output
10.7 by 10.9 by 9.1 cm
(4.2 by 4.3 by 3.6 in.)
Weight................................................. 100 g (3.5 oz)
Specifications
Typical for -40 to 60 °C unless otherwise noted.
Input Characteristics
Input channels.....................................
Input type
cFP-CTR-500....................................
cFP-CTR-502....................................
Maximum input voltage......................
Input threshold level
cFP-CTR-500....................................
12 (8 count, 4 gate)
10 to 30 VDC, sinking
5 to 30 VDC, sourcing
30 VDC
8 V typ
6 V min
10 V max
cFP-CTR-502.................................... V
SUP
– 2.5 V typ
V
SUP
– 3.0 V min
V
SUP
– 2.0 V max
(V
SUP
is the external supply voltage)
Input current limiting
cFP-CTR-500.................................... 5 mA
cFP-CTR-502.................................... 6 mA
Input bandwidth
Count inputs.................................... 50 kHz or software-enabled
200 kHz lowpass filter
Gate inputs ..................................... 50 kHz
Maximum off-state leakage current for external devices
cFP-CTR-500.................................... 0.2 mA
cFP-CTR-502.................................... 0.3 mA
Isolation Voltage
Maximum isolation voltage ................ 250 V
rms
, Installation Category II
Channel-to-channel isolation.............. No isolation between channels
Transient overvoltage.......................... 2,300 V
rms
Environment
Operating temperature ....................... -40 to 60 °C
Storage temperature........................... -55 to 85 °C
Relative humidity ................................ 10 to 90%, noncondensing
Shock and Vibration
Operating vibration, random
(IEC 60068-2-64) ............................. 10 to 500 Hz, 5 g
rms
Operating vibration, sinusoidal
(IEC 60068-2-6) ............................... 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27) ............................. 50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations
Output Characteristics
Output channels.................................. 4
Output type
cFP-CTR-500.................................... 10 to 30 VDC sourcing,
compatible with most
12 and 24 VDC devices
cFP-CTR-502.................................... 5 to 30 VDC sinking, compatible
with TTL and other 5, 12, and
24 VDC devices
Supply voltage
cFP-CTR-500.................................... 10 to 30 VDC, user-provided
cFP-CTR-502.................................... 5 to 30 VDC, user-provided
Maximum output current .................... 1 A per channel at -40 to 50 °C;
0.75 A per channel at 50 to 60 °C
Maximum output
current on all channels ....................... 4 A
Output impedance
cFP-CTR-500.................................... 0.3
cFP-CTR-502.................................... 0.12
Output bandwidth ............................... 16 kHz for a current flow
≥3.2
mA
Maximum off-state leakage current... 25 µA
Power Requirement
Power from network module .............. 800 mW
BUY ONLINE