Industrial Controllers
Specifications
Electrical
Voltage ..................................................
Power ....................................................
10 to 30 VDC
40 W maximum (no PCI board installed)
Note:
For UL and other safety certifications, refer to the product label or visit
ni.com/certification
, search by model number or product line, and click the
appropriate link in the Certification column.
Electromagnetic Compatibility
This product is designed to meet the requirements of the following standards of
EMC for electrical equipment for measurement, control, and laboratory use:
EN 61326 (IEC 61326): Class A emissions; Basic immunity
EN 55011 (CISPR 11): Group 1, Class A emissions
AS/NZS CISPR 11: Group 1, Class A emissions
FCC 47 CFR Part 15B: Class A emissions
ICES-001: Class A emissions
Note:
For EMC compliance, operate this device according to
product documentation.
Physical
Unit dimensions ....................................
Weight...................................................
110 by 200 by 220 cm
(4.3 by 7.9 by 8.66 in.)
3.63 kg (8.0 lb) maximum
(no PCI board installed)
Environment
Maximum altitude .................................
Pollution degree ....................................
Indoor use only.
2,000 m (at 25 °C ambient temperature)
2
CE Compliance
This product meets the essential requirements of applicable European Directives,
as amended for CE marking, as follows:
2006/95/EC; Low-Voltage Directive (safety)
2004/108/EC; Electromagnetic Compatibility Directive (EMC)
Note:
Refer to the Declaration of Conformity (DoC) for this product for any
additional regulatory compliance information. To obtain the DoC for this product,
visit
ni.com/certification
, search by model number or product line, and click
the appropriate link in the Certification column.
Operating Environment
No PCI board installed ..........................
PCI board installed (10 W max).............
heat sink at the top.
0 to 50 °C
0 to 45 °C
Note:
Thermal performance is orientation-dependent and was tested with the
Storage Environment
Ambient temperature ............................
Relative humidity ..................................
-40 to 70 °C (tested in accordance with
IEC-60068-2-1 and IEC-60068-2-2)
5 to 95% noncondensing (tested in
accordance with IEC-60068-2-56)
Online Product Certification
Refer to the product Declaration of Conformity (DoC) for additional regulatory
compliance information. To obtain product certifications and the DoC for this
product, visit
ni.com/certification,
search by model number or product line,
and click the appropriate link in the Certification column.
Shock and Vibration
Functional shock....................................
30 g peak, 11 ms pulse
(tested in accordance with
IEC-60068-2-27; test profile developed
in accordance with MIL-PRF-28800F)
Environmental Management
NI is committed to designing and manufacturing products in an environmentally
responsible manner. NI recognizes that eliminating certain hazardous substances
from our products is beneficial to the environment and to NI customers.
For additional environmental information, refer to the NI and the Environment
Web page at
ni.com/environment.
This page contains the environmental
regulations and directives with which NI complies, as well as other
environmental information not included in this document.
Random Vibration
Operating vibration ...............................
Nonoperating vibration .........................
5 to 500 Hz, 0.31 g
rms
5 to 500 Hz, 2.4 g
rms
(tested in accordance with
IEC-60068-2-64; nonoperating test
profile exceeds the requirements of
IL-PRF-28800F, Class 3)
Waste Electrical and Electronic Equipment (WEEE)
EU Customers:
At the end of their life cycle, all products must be
sent to a WEEE recycling center. For more information about WEEE
recycling centers and National Instruments WEEE initiatives,
visit
ni.com/environment/weee.htm
.
Safety and Compliance
Safety
This product is designed to meet the requirements of the following standards of
safety for electrical equipment for measurement, control, and laboratory use:
IEC 61010-1, EN 61010-1
UL 61010-1, CSA 61010-1