Digital Output Modules for Compact FieldPoint
Environment
Operating temperature ....................... -40 to 70 °C
Storage temperature........................... -55 to 85 °C
Relative humidity ................................ 10 to 90%, noncondensing
Specifications
Typical for -40 to 70 °C unless otherwise noted.
Digital Output Channels
Number of output channels
cFP-DO-400, cFP-DO-410 ................ 8
cFP-DO-401, cFP-DO-403 ................ 16
Voltage range...................................... 5 to 30 VDC
Output impedance at 10 to 30 V ........ 0.3 (0.3 V drop at 1 A)
cFP-DO-403 ..................................... 0.12
Output impedance at 5 to 10 V .......... 2
Maximum output current per channel at 10 to 30 V range
cFP-DO-400, cFP-DO-401 ................ 1.5 A
cFP-DO-403 ..................................... 2.0 A
cFP-DO-410 ..................................... 1 A
Maximum output current on all channels
cFP-DO-400 ..................................... 8 A
2
cFP-DO-401 ..................................... 8 A
2
cFP-DO-403 ..................................... 16 A
2
at -40 to 60 °C
12 A
2
at 60 to 70 °C
cFP-DO-410 ..................................... 8 A
Maximum output current at 5 to 10 V range
Per channel ..................................... 0.67 A
All channels, cFP-DO-400
1
.............. 1.35 A
2
All channels, cFP-DO-401
1
.............. 1.2 A
2
Output delay time
Turn ON........................................... 20 µs
Turn OFF .......................................... 50 µs
Protection
Flyback diode to COM for inductive loads
Leakage, overcurrent condition
Power-on state.................................... Off, until set to power-on state
stored in local network module
1
The
Shock and Vibration
Operating vibration, random
(IEC 60068-2-64) ............................. 10 to 500 Hz, 5 g
rms
Operating vibration, sinusoidal
(IEC 60068-2-6) ............................... 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27) ............................. 50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations
Safety and Compliance
Safety
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement, control,
and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 61010-1, CSA 61010-1
Note:
For UL and other safety certifications, refer to the product label or
visit
ni.com/certification,
search by model number or product line, and
click the appropriate link in the Certification column.
Electromagnetic Compatibility
This product is designed to meet the requirements of the following
standards of EMC for electrical equipment for measurement, control,
and laboratory use:
• EN 61326 EMC requirements; Minimum Immunity
• EN 55011 Emissions; Group 1, Class A
• CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A
Note:
For EMC compliance, operate this device according to
product documentation.
sum of the squares of the output currents on every channel must be less than or equal
to this value.
Power Requirements
Power from network module
cFP-DO-400 ..................................... 300 mW
cFP-DO-401 and cFP-DO-403.......... 600 mW
cFP-DO-410 ..................................... 400 mW
CE Compliance
This product meets the essential requirements of applicable European
Directives, as amended for CE marking, as follows:
• 2006/95/EC; Low-Voltage Directive (safety)
• 2004/108/EC; Electromagnetic Compatibility Directive (EMC)
Note:
Refer to the Declaration of Conformity (DoC) for this product for
any additional regulatory compliance information. To obtain the DoC for
this product, visit
ni.com/certification,
search by model number or
product line, and click the appropriate link in the Certification column.
Isolation Voltage
Channel-to-channel isolation.............. No isolation between channels
Transient overvoltage.......................... 2,300 V
rms
Physical Characteristics
LED indicators
POWER (green) ...............................
READY (green) ................................
<0...15> or <0...7> (green) ..............
Dimensions (including terminal base)
Power on and self-test passed
Module configured and ready
On/off state of each channel
10.7 by 10.9 by 9.1 cm
(4.2 by 4.3 by 3.6 in.)
Weight................................................. 136 g (4.8 oz)
Waste Electrical and Electronic Equipment (WEEE)
EU Customers:
At the end of their life cycle, all products must be
sent to a WEEE recycling center. For more information about WEEE
recycling centers and National Instruments WEEE initiatives,
visit
ni.com/environment/weee.htm.
BUY ONLINE
at
ni.com
or
CALL 800 813 3693 (U.S.)
3