欢迎访问ic37.com |
会员登录 免费注册
发布采购

450-XS6DT3 参数 Datasheet PDF下载

450-XS6DT3图片预览
型号: 450-XS6DT3
PDF下载: 下载PDF文件 查看货源
内容描述: 柴油机发电机组 [Diesel Engine-Generator Set]
分类和应用: 电机
文件页数/大小: 4 页 / 426 K
品牌: MTU [ MTU ONSITE ENERGY CORPORATION ]
 浏览型号450-XS6DT3的Datasheet PDF文件第1页浏览型号450-XS6DT3的Datasheet PDF文件第2页浏览型号450-XS6DT3的Datasheet PDF文件第4页  
3
// /
/
450-XS6dt3
aPPlication Data
//
Engine
MTU Detroit Diesel
Series 60
(6063HV35)
4-Cycle
6-Inline
855 (14)
5.24 (13.3)
6.61 (16.8)
16:1
1,800
DDEC
685 (511)
±.25%
60 Hz
Dry
//
Fuel Consumption
34.6 (131)
26.4 (100)
18.2 (69)
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Regulation
Frequency
Air Cleaner
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
//
Cooling - radiator System
122 (50)
0.5 (0.12)
96 (363)
9,400 (165)
7,250 (127)
6,145 (108)
Ambient Capacity of Radiator: °F (°C)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H
2
0 (kPa)
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Radiated to Air to Air: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
//
//
Liquid Capacity (Lubrication)
9.5 (36)
6 (23)
42 (159)
Air requirements
1,395 (39.5)
25,304 (717)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
Aspirating: *SCFM (m
3
/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m
3
/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m
3
/min)
* Air density = 0.0739 lbm/ft
3
(1.184 kg/m
3
)
13,859 (395)
//
Electrical
24
950
//
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
Exhaust System
1,058 (570)
3,973 (112.5)
40.8 (10.2)
//
Fuel System
1/2” NPT
1/2” NPT
6.8 (2.1)
Diesel #2
90.8 (344)
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m
3
/min)
Maximum Allowable
Back Pressure: in. H
2
0 (kPa)