3
// /
/
350-JC6dt3
APPLICATION DATA
//
Engine
John Deere
6135HF485
4-Cycle
6-Inline
824 (13.5)
5.2 (13.2)
6.5 (16.5)
16:1
1,800
JDEC
538 (401)
489 (365)
±.25%
60 Hz
Dry
//
Fuel Consumption
STANDBY
26.4 (99.9)
19.3 (73.1)
13.7 (51.9)
PRIME
23.2 (87.81)
17.4 (65.86)
12.5 (47.31)
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
//
Cooling - radiator System
STANDBY
122 (50)
0.5 (0.12)
124 (470)
11,042 (194)
6,033 (106)
2,417 (42.5)
PRIME
122 (50)
0.5 (0.12)
124 (470)
10,359 (182)
5,237 (92)
2,089 (36.7)
Ambient Capacity of Radiator: °F (°C)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H
2
0 (kPa)
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Rejection to Air to Air: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
//
Liquid Capacity (Lubrication)
//
Air requirements
STANDBY
1,165 (33)
21,766 (616)
PRIME
1,059 (30)
21,766 (616)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
15.9 (60)
4.8 (18)
17.2 (65)
//
Electrical
24
925
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
Aspirating: *SCFM (m
3
/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m
3
/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m
3
/min)
5,450 (155)
4,710 (134)
* Air density = 0.0739 lbm/ft
3
(1.184 kg/m
3
)
//
Fuel System
3/4” NPT
1/2” NPT
3.3 (1)
Diesel #2
47.5 (179.8)
//
Exhaust System
STANDBY
835 (446)
2,648 (75)
40 (10)
PRIME
783 (417)
2,295 (65)
40 (10)
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m
3
/min)
Maximum Allowable
Back Pressure: in. H
2
0 (kPa)