欢迎访问ic37.com |
会员登录 免费注册
发布采购

300-XC6DT3 参数 Datasheet PDF下载

300-XC6DT3图片预览
型号: 300-XC6DT3
PDF下载: 下载PDF文件 查看货源
内容描述: 柴油机发电机组 [DIESEL ENGINE-GENERATOR SET]
分类和应用: 电机
文件页数/大小: 4 页 / 446 K
品牌: MTU [ MTU ONSITE ENERGY CORPORATION ]
 浏览型号300-XC6DT3的Datasheet PDF文件第1页浏览型号300-XC6DT3的Datasheet PDF文件第2页浏览型号300-XC6DT3的Datasheet PDF文件第4页  
3
// /
/
300-XC6dt3
APPLICATION DATA
//
Engine
MTU Detriot Diesel
Series 60
(6063HV35)
4-Cycle
6-Inline
855 (14)
5.24 (13.3)
6.61 (16.8)
16:1
1,800
DDEC
490 (366)
424 (316)
±.25%
60 Hz
Dry
//
Fuel Consumption
STANDBY
25.4 (96)
20.2 (76)
13.7 (52)
PRIME
22.7 (86)
17.3 (66)
11.6 (44)
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
//
Cooling - radiator System
STANDBY
122 (50)
0.5 (0.12)
96 (363)
7,950 (140)
5,150 (90)
5,276 (93)
PRIME
122 (50)
0.5 (0.12)
96 (363)
7,000 (123)
4,750 (83)
4,930 (86.7)
Ambient Capacity of Radiator: °F (°C)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H
2
0 (kPa)
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Rejection to Air to Air: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
//
Liquid Capacity (Lubrication)
9.5 (36)
6 (23)
42 (159)
//
Air requirements
STANDBY
1,105 (31)
PRIME
1,070 (30)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//
Electrical
24
950
Aspirating: *SCFM (m /min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m
3
/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m
3
/min)
3
18,891 (535) 18,891 (535)
11,899 (339) 11,118 (317)
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
* Air density = 0.0739 lbm/ft
3
(1.184 kg/m
3
)
//
//
Fuel System
1/2” NPT
1/2” NPT
6.7 (2.1)
Diesel #2
86.9 (329)
Exhaust System
STANDBY
944 (507)
2,903 (82)
40.8 (10.16)
PRIME
871 (466)
2,657 (75)
40.8 (10.16)
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m
3
/min)
Maximum Allowable
Back Pressure: in. H
2
0 (kPa)