A tognum grouP BrAnd
DIESEL ENGINE-GENERATOR SET
1500-XC6DT2
1500 ekW
/
60 Hz
/
Standby
1400 ekW
/
60 Hz
/
Prime
480 - 4160V
SySTEm RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
480V**
3
0.8
60
1500
1875
2255
3500
742RSL4050
130°C/27°C
4 BAR WYE
600V**
3
0.8
60
1500
1875
1804
4800
743RSS4290
125°C/40°C
4 LEAD WYE
4160V
3
0.8
60
1500
1875
260
3900
743FSM4368
130°C/27°C
6 LEAD WYE
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
480V
3
0.8
60
1400
1750
2105
3500
742RSL4050
105°C/40°C
12 LEAD HI WYE
600V
3
0.8
60
1400
1750
1684
4800
743RSS4290
105°C/40°C
4 LEAD WYE
4160V
3
0.8
60
1400
1750
243
3900
743FSM4368
105°C/40°C
6 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered