A tognum group BrAnd
Diesel engine-generator set
125-Js6Dt3
125 ekW
/
60 Hz
/
Standby
208 - 600V
system ratings
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
** UL2200 Offered
240V**
1
1.0
60
125
125
521
136
431CSL6204
130°C/27°C
12 LEAD ZIG-ZAG
240V**
1
1.0
60
125
125
521
195
431CSL6224
130°C/27°C
4 LEAD
208V**
3
0.8
60
125
156.25
434
250
363CSL1607
130°C/27°C
12 LEAD LOW WYE
240V**
3
0.8
60
125
156.25
376
250
363CSL1607
130°C/27°C
12 LEAD HI DELTA
480V**
3
0.8
60
125
156.25
188
330
363CSL1607
130°C/27°C
12 LEAD HI WYE
600V**
3
0.8
60
125
156.25
150
335
363PSL1658
125°C/40°C
4 LEAD WYE
FACTS
//
//
//
//
//
//
//
//
//
EPA Tier 3 Certified
Engine-Generator Set Tested to ISO 8528-5 for
transient response
UL2200, CSA Listing Offered
Accepts Rated Load in One Step Per NFPA 110, Level 1
All engine-generator sets are prototype and factory tested
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
6068HF285 Diesel Engine
- 6.8 Liter Displacement
- 4-Cycle
Complete Range of Accessories
Permanent Magnet Generator (PMG) - Optional
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
//
Digital Control Panel(s)
- UL Recognized,
, NFPA 110
- Complete System Metering
- LCD Display
//
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
//
//