/ // /
4
125-JC6ꢄꢀ3
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design.
System
ꢄimensiꢅns (LxWxH)
Weiꢆht (less tank)
OPU
105 x 36 x 52 in (2,670 x 910 x 1,320 mm)
2,821 lb (1,280 kg)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
unit ꢀype
Standby Fꢇll Lꢅad
Standby ꢁꢅ Lꢅad
Prime Fꢇll Lꢅad
Prime ꢁꢅ Lꢅad
OPU w/Critical Grade Muffler (dBA)
Sound Attenuated Enclosure (dBA)
Measurements for sound data are taken at 23 ft (7 m).
91.5
83.5
84
76
90
82
84
76
EmISSIONS DATA
RATING DEFINITIONS AND CONDITIONS
//
ꢁox + ꢁꢂHC
Co
Pꢂ
Ambient capability factor at 984 ft (300 m). Consult your
2.65
0.98
0.13
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload capa-
bility for this rating. Ratings are in accordance with
ISO-3046/1, BS 5514, AS 2789, and DIN 6271.
//
All ꢇnits are in ꢆ/hp-hr and are EPA ꢄ2 cycle valꢇes.
Emission levels of the engine may vary as a function of ambi-
ent temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one engine
representing this rating. The data was obtained under cont-
rolled environmental conditions with calibrated instrumentation
traceable to the United States National Bureau of Standards
and in compliance with US EPA regulations found within 40 CFR
Part 89. The weighted cycle value from each engine is guaran-
teed to be below the US EPA Standards at the US EPA defined
conditions.
//
Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO-8528/1, overload power in accordance
with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For
limited running time and base load ratings, consult the
factory.
//
Deration Factor:
Altitꢇde: 0.5% per 1,000 ft (305 m) above 5,000 ft (1,524 m)
and 4% per 1,000 ft (305 m) above 10,000 ft (3,048 m).
ꢀemperatꢇre: 0.5% per 10°F (5.5°C) above 77°F (25°C).
Materials and specifications subject to change without notice.
// ꢀꢅꢆnꢇm grꢅꢇp Cꢅmpanies: Eꢇrꢅpe / ꢂiddle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 /
Fax +49 7541 90 7084 / powergenregion1@mtu-online.com // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore /
Phone + 65 6861 5922 / Fax + 65 6861 3615 / powergenregion2@mtu-online.com // uSA / Canada / ꢂexicꢅ / MTU Onsite Energy / 100 Power Drive / Mankato, Minnesota
56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / powergenregion3@mtu-online.com // Wꢅrldwide fꢅr Hꢅtꢂꢅdꢇle / MTU Onsite Energy / 81663 Munich /
Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / info@cfc-solutions.com //www.mtu-online.com