960W Three Phase Industrial DIN RAIL Power Supply
Features :
D R T- 9 6 0
series
Three-Phase AC 340 ~ 550V wide range input
High efficiency 91% and low dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Optional parallel function(1+1)
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
R
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (max.)
LEAKAGE CURRENT
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
SAFETY &
EMC
(Note 4)
DRT-960-24
24V
40A
0 ~ 40A
960W
24 ~ 28V
1.0%
0.5%
0.5%
200ms, 60ms/400VAC
200ms, 60ms/500VAC at full load
DRT-960-48
48V
20A
0 ~ 20A
960W
80mVp-p
48 ~ 55V
1.0%
0.5%
0.5%
RIPPLE & NOISE (max.)
Note.2
80mVp-p
14ms/400VAC
30ms/500VAC at full load
Three-Phase 340 ~ 550VAC (Dual phase operation possible in connecting L1,L3,FG
Note.5
)
47 ~ 63Hz
91%
2A/400VAC
1.6A/500VAC
COLD START 50A
<3.5mA / 530VAC
105 ~ 125% rated output power
Protection type : Constant current limiting, unit will shut down o/p voltage after 3 sec. , re-power on to recover
30 ~ 36V
59 ~ 66V
Protection type : Shut down o/p voltage, re-power on to recover
110
5 (TSW1) Detect on heatsink of power transistor
85
-20 ~ +60
-40 ~ +85
(Refer to output load derating curve)
, 10 ~ 95% RH
5
(TSW2) Detect on heatsink of power diode
92%
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
20 ~ 90% RH non-condensing
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 Approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
HARMONIC CURRENT
EMS IMMUNITY
MTBF
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
122.5Khrs min. MIL-HDBK-217F (25 )
276*125.2*100mm (W*H*D)
3.3Kg; 4pcs/14.2Kg/1.14CUFT
OTHERS
NOTE
DIMENSION
PACKING
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Dual phase operation(connecting L1,L3,FG)is allowed under certain derating to output load. Please refer to the derating curves for details.
File Name:DRT-960-SPEC 2007-01-12