型号: DRT-480-24
PDF下载: 下载PDF文件 查看货源
内容描述: 480W三相工业DIN导轨式电源供应 [480W Three Phase Industrial DIN RAIL Power Supply]
分类和应用:
文件页数/大小: 2 页 / 285 K
品牌: MEANWELL [ MEAN WELL ENTERPRISES CO., LTD. ]
 浏览型号DRT-480-24的Datasheet PDF文件第2页  
480W Three Phase Industrial DIN RAIL Power Supply
Features :
D R T- 4 8 0
series
Three-Phase AC 340 ~ 550V wide range input
High efficiency 89% and low dissipation
Protections:Short circuit/Over load/Over voltage/Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
R
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER LOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
DRT-480-24
24V
20A
0 ~ 20A
480W
24 ~ 28V
1.0%
0.5%
0.5%
1200ms, 40ms/400VAC
16ms/400VAC
47 ~ 63Hz
89%
1.7A/400VAC
1.3A/500VAC
COLD START 50A
<3.5mA / 530VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
30 ~ 36V
59 ~ 66V
Protection type : Shut down o/p voltage, re-power on to recover
110
5 (TSW) Detect on heatsink of power switch
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70
-40 ~ +85
0.03%/
(Refer to output load derating curve)
, 10 ~ 95% RH
(0 ~ 50
20 ~ 90% RH non-condensing
90%
Three-Phase 340 ~ 550VAC
800ms, 40ms/500VAC at full load
480 ~ 780VDC
35ms/500VAC at full load
DRT-480-48
48V
10A
0 ~ 10A
480W
80mVp-p
48 ~ 55V
1.0%
0.5%
0.5%
RIPPLE & NOISE (max.)
Note.2
80mVp-p
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 Approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
SAFETY & ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
EMC
(Note 4)
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
91.1Khrs min. MIL-HDBK-217F (25
227*125.2*100mm (W*H*D)
2.5Kg; 6pcs/16Kg/1.75CUFT
)
OTHERS
NOTE
DIMENSION
PACKING
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Dual phase operation: derating of 20% is required.
File Name:DRT-480-SPEC 2005-09-06