LC/LW010- and LC/LW015-Series Power Modules:  
18 Vdc to 36 Vdc or 36 Vdc to 75 Vdc Inputs, 10 W and 15 W  
Data Sheet  
March 27, 2008  
Current Limit  
Design Considerations  
Input Source Impedance  
To provide protection in a fault (output overload) condi-  
tion, the unit is equipped with internal current-limiting  
circuitry and can endure current limiting for an unlim-  
ited duration. At the point of current-limit inception, the  
unit shifts from voltage control to current control. If the  
output voltage is pulled very low during a severe fault,  
the current-limit circuit can exhibit either foldback or  
tailout characteristics (output-current decrease or  
increase). The unit operates normally once the output  
current is brought back into its specified range.  
The power module should be connected to a low  
ac-impedance input source. Highly inductive source  
impedances can affect the stability of the power mod-  
ule. If the source inductance exceeds 4 µH, a 33 µF  
electrolytic capacitor (ESR < 0.7 Ω at 100 kHz)  
mounted close to the power module helps ensure  
stability of the unit.  
Safety Considerations  
Remote On/Off (Optional)  
For safety-agency approval of the system in which the  
power module is used, the power module must be  
installed in compliance with the spacing and separation  
requirements of the end-use safety agency standard,  
i.e., UL 1950, CSA 22.2 No. 950-95, EN60950, and  
IEC950.  
Two remote on/off options are available. Positive logic,  
device code suffix “4”, remote on/off turns the module  
on during a logic-high voltage on the remote ON/OFF  
pin, and off during a logic low. Negative logic, device  
code suffix “1”, remote on/off turns the module off dur-  
ing a logic high and on during a logic low.  
For the converter output to be considered meeting the  
requirements of safety extra-low voltage (SELV), one of  
the following must be true of the dc input:  
To turn the power module on and off, the user must  
supply a switch to control the voltage between the  
on/off terminal and the VI(–) terminal (Von/off). The  
switch may be an open collector or equivalent (see  
Figure 38). A logic low is Von/off = –0.7 V to +1.2 V. The  
maximum Ion/off during a logic low is 1 mA. The switch  
should maintain a logic-low voltage while sinking 1 mA.  
n All inputs are SELV and floating, with the output also  
floating.  
n All inputs are SELV and grounded, with the output  
also grounded.  
During a logic high, the maximum Von/off generated by  
the power module is 10 V. The maximum allowable  
leakage current of the switch at Von/off = 10 V is 50 µA.  
n Any non-SELV input must be provided with rein-  
forced insulation from any other hazardous voltages,  
including the ac mains, and must have a SELV reli-  
ability test performed on it in combination with the  
converters.  
The module has internal capacitance to reduce noise  
at the ON/OFF pin. Additional capacitance is not gen-  
erally needed and may degrade the start-up character-  
istics of the module.  
The power module has extra-low voltage (ELV) outputs  
when all inputs are ELV.  
The input to these units is to be provided with a maxi-  
mum 5 A normal-blow fuse in the ungrounded lead.  
VI(+)  
VI(-)  
-
Feature Descriptions  
Von/off  
+
Output Overvoltage Clamp  
REMOTE  
ON/OFF  
Ion/off  
The output overvoltage clamp consists of control cir-  
cuitry, independent of the primary regulation loop, that  
monitors the voltage on the output terminals. This con-  
trol loop has a higher voltage set point than the primary  
loop (see Feature Specifications table). In a fault condi-  
tion, the overvoltage clamp ensures that the output  
voltage does not exceed VO, clamp, max. This provides a  
redundant voltage-control that reduces the risk of  
output overvoltage.  
8-758(C).a  
Figure 38. Remote On/Off Implementation  
Lineage Power  
15  