Data Sheet
KNW013-020 Series Power Modules:
June 29, 2009
36 – 75Vdc Input; 3.3 to 5.0Vdc Output; 13 to 20A Output Current
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are
absolute stress ratings only, functional operation of the device is not implied at these or any other conditions in
excess of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for
extended periods can adversely affect the device reliability.
Parameter
Device
Symbol
Min
Max
Unit
Operating Input Voltage
Continuous
All
All
VIN
-0.3
-0.3
80
Vdc
Vdc
Transient (100 ms)
VIN,trans
100
Operating Ambient Temperature
(see Thermal Considerations section)
All
TA
-40
85
°C
Storage Temperature
All
All
Tstg
-55
125
°C
⎯
⎯
I/O Isolation voltage (100% Factory Hi-Pot tested)
2250
Vdc
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature
conditions.
Parameter
Device
Symbol
Min
Typ
Max
Unit
Operating Input Voltage
All
VIN
36
48
75
Vdc
Adc
Maximum Input Current
All
All
IIN,max
1.7
45
2.4
(VIN= VIN, min to VIN, max, IO=IO, max
)
Input No Load Current
IIN,No load
mA
mA
(VIN = VIN, nom, IO = 0, module enabled)
Input Stand-by Current
All
All
IIN,stand-by
I2t
6
8
(VIN = VIN, nom, module disabled)
Inrush Transient
0.1
A2s
mAp-p
dB
Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 1μH source impedance; VIN, min to
All
All
30
60
VIN, max, IO= IOmax ; See Test configuration section)
Input Ripple Rejection (120Hz)
EMC, EN55022
See EMC Considerations section
CAUTION: This power module is not internally fused. An input line fuse must always be used.
This power module can be used in a wide variety of applications, ranging from simple standalone operation to an
integrated part of sophisticated power architectures. To preserve maximum flexibility, internal fusing is not included,
however, to achieve maximum safety and system protection, always use an input line fuse. The safety agencies
require a time-delay fuse with a maximum rating of 5 A (see Safety Considerations section). Based on the
information provided in this data sheet on inrush energy and maximum dc input current, the same type of fuse with a
lower rating can be used. Refer to the fuse manufacturer’s data sheet for further information.
LINEAGE POWER