Data Sheet  
JNW350R Power Modules; DC-DC Converters  
36 – 75 Vdc Input; 28Vdc Output; 350W Output  
July 27, 2009  
Safety Considerations (continued)  
For all input sources, other than DC MAINS, where  
the input voltage is between 60 and 75V dc  
(Classified as TNV-2 in Europe), the following must  
be meet, if the converter’s output is to be evaluated  
for SELV:  
ƒ
ƒ
ƒ
The input source is to be provided with reinforced  
insulation from any hazardous voltage, including  
the ac mains.  
One Vi pin and one Vo pin are to be reliably  
earthed, or both the input and output pins are to  
be kept floating.  
Figure 10. Circuit configuration for using Remote  
On/Off Implementation.  
Overcurrent Protection  
Another SELV reliability test is conducted on the  
whole system, as required by the safety  
agencies, on the combination of supply source  
and the subject module to verify that under a  
single fault, hazardous voltages do not appear at  
the module’s output.  
To provide protection in a fault output overload  
condition, the module is equipped with internal current  
limiting protection circuitry, and can endure  
overcurrent transient overloads depending upon the  
duration and amplitude of the overload. An internal  
buffer measures the relative product of the duration  
and amplitude of the overload and allows operation  
until a limit threshold is reached. For lower amplitude  
overloads, the module will operate without shutdown  
for a longer transient overload. If the overload  
amplitude is larger, the module will reach shutdown in  
a shorter period of time.  
All flammable materials used in the manufacturing of  
these modules are rated 94V-0, or tested to the  
UL60950 A.2 for reduced thickness.  
The input to these units is to be provided with a  
maximum 20 A fast-acting or time-delay fuse in the  
unearthed lead.  
A latching shutdown option is standard. If overcurrent  
persists for beyond the overload buffer, the module  
will  
shut down and remain off until the module is reset by  
either cycling the input power or by toggling the on/off  
pin for one second.  
Feature Description  
Remote On/Off  
An auto-restart option (4) is also available in a case  
where an auto recovery is required. If overcurrent  
persists for few milli-seconds, the module will shut  
down and auto restart until the fault condition is  
corrected. If the output overload condition still exists  
when the module restarts, it will shut down again. This  
operation will continue indefinitely, until the  
Two remote on/off options are available. Positive logic  
turns the module on during a logic high voltage on the  
ON/OFF pin, and off during a logic low. Negative logic  
remote On/Off, device code suffix “1”, turns the  
module off during a logic high and on during a logic  
low.  
overcurrent condition is corrected.  
To turn the power module on and off, the user must  
supply a switch (open collector or equivalent) to  
control the voltage (Von/off) between the ON/OFF  
terminal and the VIN(-) terminal (see Figure 10). Logic  
low is 0V Von/off 1.2V. The maximum Ion/off during a  
logic low is 1mA, the switch should be maintain a  
logic low level whilst sinking this current.  
Over Voltage Protection  
The output overvoltage protection consists of circuitry  
that monitors the voltage on the output terminals. If  
the voltage on the output terminals exceeds the over  
voltage protection threshold, then the module will  
shutdown and latch off. The overvoltage latch is reset  
by either cycling the input power for one second or by  
toggling the on/off signal for one second. The  
During a logic high, the typical maximum Von/off  
generated by the module is 5V, and the maximum  
allowable leakage current at Von/off = 5V is 50μA.  
protection mechanism is such that the unit can  
continue in this condition until the fault is cleared.  
If not using the remote on/off feature:  
For positive logic, leave the ON/OFF pin open.  
For negative logic, short the ON/OFF pin to VIN(-).  
An auto-restart option (4) is also available in a case  
where an auto recovery is required.  
LINEAGE POWER  
7