Data Sheet  
JHC/JHW350 Power Module; dc-dc Converter  
March 26, 2008  
18 – 36Vdc or 36 – 75Vdc Input; 28Vdc Output; 350W  
fast-acting (or time-delay) fuse in the unearthed lead  
for their respective versions.  
Safety Considerations  
All Versions - For safety-agency approval of the  
system in which the power module is used, the power  
module must be installed in compliance with the  
spacing and separation requirements of the end-use  
safety agency standard, i.e., UL60950, CSA C22.2  
No. 60950-00, and EN 60950 (VDE 0805):2001-12.  
Feature Descriptions  
Overcurrent Protection  
To provide protection in a fault output overload  
condition, the module is equipped with internal  
current-limiting circuitry and can endure current limit  
for few seconds. If overcurrent persists for few  
seconds, the module will shut down and remain latch-  
off. The overcurrent latch is reset by either cycling the  
input power or by toggling the on/off pin for one  
second. If the output overload condition still exists  
when the module restarts, it will shut down again. This  
operation will continue indefinitely until the  
“W” Versions only - For end products connected to –  
48V dc, or –60Vdc nominal DC MAINS (i.e. central  
office dc battery plant), no further fault testing is  
required. *Note: -60V dc nominal battery plants are  
not available in the U.S. or Canada.  
All Versions - For all input voltages, other than DC  
MAINS, where the input voltage is less than 60V dc, if  
the input meets all of the requirements for SELV,  
then:  
overcurrent condition is corrected.  
ƒ
The output may be considered SELV. Output  
voltages will remain within SELV limits even  
with internally-generated non-SELV voltages.  
Single component failure and fault tests were  
performed in the power converters.  
An auto-restart option is also available.  
Remote On/Off  
Two remote on/off options are available. Positive logic  
remote on/off turns the module on during a logic-high  
voltage on the ON/OFF pin, and off during a logic low.  
Negative logic remote on/off turns the module off  
during a logic high and on during a logic low. Negative  
logic, device code suffix "1," is the factory-preferred  
configuration. To turn the power module on and off,  
the user must supply a switch to control the voltage  
between the on/off terminal (Von/off) and the VI (-)  
terminal. The switch can be an open collector or  
equivalent (see Figure 16). A logic low is Von/off = 0  
V to 0.5 V. The maximum Ion/off during a logic low is  
1 mA. The switch should maintain a logic-low voltage  
while sinking 1 mA. During a logic high, the maximum  
Von/off generated by the power module is 5 V. The  
maximum allowable leakage current of the switch at  
Von/off = 5V is 50 µA. If not using the remote on/off  
feature, perform one of the following to turn the unit  
on:  
ƒ
One pole of the input and one pole of the  
output are to be grounded, or both circuits are  
to be kept floating, to maintain the output  
voltage to ground voltage within ELV or SELV  
limits.  
“W” Versions only - For all input sources, other than  
DC MAINS, where the input voltage is between 60  
and 75V dc (Classified as TNV-2 in Europe), the  
following must be meet, if the converter’s output is to  
be evaluated for SELV:  
ƒ
ƒ
ƒ
The input source is to be provided with  
reinforced insulation from any hazardous voltage,  
including the ac mains.  
One Vi pin and one Vo pin are to be reliably  
earthed, or both the input and output pins are to  
be kept floating.  
For negative logic, short ON/OFF pin to VIN(-).  
For positive logic: leave ON/OFF pin open.  
Another SELV reliability test is conducted on  
the whole system, as required by the safety  
agencies, on the combination of supply source  
and the subject module to verify that under a  
single fault, hazardous voltages do not appear at  
the module’s output.  
All Versions - The power module has ELV (extra-low  
voltage) outputs when all inputs are ELV.  
All flammable materials used in the manufacturing of  
these modules are rated 94V-0.  
Figure 16. Remote On/Off Implementation.  
The input to these units is to be provided with a  
maximum 20A (JHW series) and 30A (JHC series)  
LINEAGE POWER  
9