Output Connections  
• All field wiring should comply with the U.S. National Electrical Code (NEC) and/or applicable local codes/standards.  
• Routing of the DC output cables should guarantee that cables are not in contact with sources of heat and surfaces that may  
damage the cable insulation.  
• The DC output is not provided with a fuse or circuit breaker suitable for branch circuit protection. Therefore, the power shelf  
should be mounted in the same rack or cabinet as the equipment being powered. Use interconnecting power cables suitable for  
the application and sized to carry the rated output current. The interconnecting cables should be capable of carrying the overload  
current and short circuit current without damage or risk of fire.  
• The output for the system is SELV and has available power greater than 240VA.  
• Insulation on output field-wired conductors should be rated no less than 90°C. Wiring internal to enclosed equipment cabinets  
should be rated at 105°C (minimum). The provided DC output cords (red and black wires) are rated for 105°C.  
• Before opening the insulating cover to gain access to load and ground connections, ensure all power supplies are disconnected  
from the AC MAINS.  
AC Input Connections  
• AC branch circuits to this equipment must be protected with fuses or circuit breakers sized as required by the U.S. National  
Electric Code (NEC) and/or local codes. Up to four AC mains power cords are required to power the shelf (one for each rectifier).  
Each power cord should be connected to a separate AC mains branch circuit with an overcurrent protector rated at no more than  
20A.  
• The power supply mains inlet may be used as the means to provide AC protective earthing.  
• An accessible AC disconnect/protection device to remove AC power from the equipment in the event of an emergency must be  
provided. An accessible socket-outlet/receptacle installed near the equipment is also acceptable as a disconnect.  
• The equipment is powered by multiple AC inputs (one per rectifier). Disconnect all AC sources of power before servicing.  
• These units are to be used with TN-S power systems only.  
German Safety Guidelines  
Installationsanleitung  
• Alle Ausgänge des Gerätes erfüllen die Anforderungen für SELV nach IEC/EN60950-1.  
• Die Ausgänge des Gerätes liegen über den Limits für Energiegefahr nach IEC/EN60950-1 (>240 VA). Das Gerät ist zum  
Einbau in ein Montage-Rack bestimmt. Siehe Einbaubestimmungen in der Montageanleitung, um eine Gefährdung des  
Benutzers während der Installation zu vermeiden.  
ACHTUNG:  
Hoher Ableitstrom Vor Anschluss an den Versorgungsstromkreis unbedingt Erdungsverbindung herstellen  
• Das Produkt ist zum Gebrauch in einer Umgebungstemperatur von max. 55°C bestimmt.  
• Die Gerätestecker des Produktes sind dazu bestimmt, eine sichere Erdung des Gerätes herzustellen.  
• Das Produkt ist zum Gebrauch in einer Umgebung mit Verschmutzungsgrad 2 nach IEC/EN60950 bestimmt.  
• Die Netzteile des Gerätes können während des Betriebes einzeln ausgetauscht werden (Hot Swapping).  
• Das Gerät wurde zusammen mit den Anschlussleitungen (ohne Anschlussstecker) geprüft. Die Installation eines Steckers des  
jeweiligen Landes, sollte nur durch geschultes Service Personal durchgeführt werden.Als alternative könnte eine Vorinstallation  
des Steckers bereits bei der Herstellung erfolgt sein.  
COMPACT POWER LINE SHELVES – MODEL J85480S1  