Data Sheet  
EUE Series DC-DC Power Modules:  
March 19, 2009  
42-55/42-58Vdc Input; 12Vdc Output; 200/120W  
Overtemperature Protection  
Feature Description  
These modules feature an overtemperature protection  
circuit to safeguard against thermal damage. The  
protection circuit shuts down the module when the  
maximum device reference temperature is exceeded.  
When the module cools down and the reference  
device temperature falls below the recovery threshold,  
the module will resume operation.  
Remote On/Off  
Two remote on/off options are available. Positive logic  
remote on/off turns the module on during a logic-high  
voltage on the ON/OFF pin, and off during a logic low.  
Negative logic remote on/off turns the module off  
during a logic high and on during a logic low. Negative  
logic, device code suffix "1," is the factory-preferred  
configuration. To turn the power module on and off,  
the user must supply a switch to control the voltage  
between the on/off terminal and the VI (-) terminal  
(Von/off). The switch can be an open collector or  
equivalent (see Figure 20). A logic low is Von/off = 0  
V to 0.8 V. The maximum Ion/off during a logic low is  
1 mA. The switch should maintain a logic-low voltage  
while sinking 1 mA. During a logic high, the maximum  
Von/off generated by the power module is 5 V. The  
maximum allowable leakage current of the switch at  
Von/off = 5V is 50 µA. If not using the remote on/off  
feature, perform one of the following to turn the unit  
on:  
Input/Output Over Voltage Protection  
The input/output overvoltage protection circuit is  
designed to shut down the module when the input  
voltage exceeds the overvoltage threshold. The  
module will resume operation when the input voltage  
enters the normal input operating range.  
Thermal Considerations  
The power modules operate in a variety of thermal  
environments and sufficient cooling should be  
provided to help ensure reliable operation.  
For negative logic, short ON/OFF pin to VI(-).  
For positive logic: leave ON/OFF pin open.  
Thermal considerations include ambient temperature,  
airflow, module power dissipation, and the need for  
increased reliability. A reduction in the operating  
temperature of the module will result in an increase in  
reliability. The thermal data presented here is based  
on physical measurements taken in a wind tunnel.  
I
on/off  
ON/OFF  
+
Von/off  
V
O
(+)  
Heat-dissipating components are mounted on the top  
side of the module. Heat is removed by conduction,  
convection and radiation to the surrounding  
environment. Proper cooling can be verified by  
measuring the thermal reference temperature (Tref ).  
Peak temperature (Tref ) occurs at the position  
indicated in Figure 21. For reliable operation this  
temperature should not exceed listed temperature  
threshold.  
LOAD  
VO  
(–)  
V
I
(+)  
VI  
(–)  
Figure 20. Circuit configuration for using Remote  
On/Off Implementation.  
Overcurrent Protection  
To provide protection in an output overload condition,  
the module is equipped with internal current-limiting  
circuitry and can endure current limiting for unlimited  
duration. If the output current exceeds the current limit  
inception value, the module enters into the hiccup  
mode operation, where it shuts down and  
automatically attempts to restart. As long as the fault  
condition exists, the module will remain in this hiccup  
mode, and can sustain this mode of operation until  
the overcurrent fault condition is corrected.  
14.50  
(.571)  
17.45  
(.687)  
EUE120: SO-8 drain pin must not exceed 115ºC.  
EUE200: LF-PAK drain tab must not exceed 120ºC.  
Figure 21. Tref Temperature Measurement  
Location for Vo=12V.  
The output power of the module should not exceed  
the rated power for the module as listed in the  
Ordering Information table.  
Input Undervoltage Lockout  
At input voltage below the input under voltage lockout  
limit, the module operation is disabled. The module  
will begin to operate at an input voltage above the  
under voltage lockout turn-on/turn-off threshold.  
Although the maximum Tref temperature of the power  
modules is 115°C for EUE120 and 120ºC for  
LINEAGE POWER  
10