 浏览型号EBVW025A0B9641-HZ的Datasheet PDF文件第4页浏览型号EBVW025A0B9641-HZ的Datasheet PDF文件第5页浏览型号EBVW025A0B9641-HZ的Datasheet PDF文件第6页浏览型号EBVW025A0B9641-HZ的Datasheet PDF文件第7页浏览型号EBVW025A0B9641-HZ的Datasheet PDF文件第9页浏览型号EBVW025A0B9641-HZ的Datasheet PDF文件第10页浏览型号EBVW025A0B9641-HZ的Datasheet PDF文件第11页浏览型号EBVW025A0B9641-HZ的Datasheet PDF文件第12页  
Data Sheet  
June 27, 2012  
EBVW025A0B Series Power Modules; DC-DC Converters  
36-75Vdc Input; 12Vdc Output; 25A Output Current  
causes the output voltage to rise above the limit in the  
Specifications Table, the module will shut down and remain  
latched off. The overvoltage latch is reset by either cycling  
the input power, or by toggling the on/off pin for one  
second. If the output overvoltage condition still exists when  
the module restarts, it will shut down again. This operation  
will continue indefinitely until the overvoltage condition is  
corrected.  
Feature Descriptions  
Overcurrent Protection  
To provide protection in a fault output overload condition,  
the module is equipped with internal current-limiting  
circuitry and can endure current limiting continuously. If the  
overcurrent condition causes the output voltage to fall  
greater than 4.0V from Vo,set, the module will shut down and  
remain latched off. The overcurrent latch is reset by either  
cycling the input power or by toggling the on/off pin for one  
second. If the output overload condition still exists when the  
module restarts, it will shut down again. This operation will  
continue indefinitely until the overcurrent condition is  
corrected.  
A factory configured auto-restart option (with overcurrent  
and overvoltage auto-restart managed as a group) is also  
available. An auto-restart feature continually attempts to  
restore the operation until fault condition is cleared.  
Overtemperature Protection  
These modules feature an overtemperature protection  
circuit to safeguard against thermal damage. The circuit  
shuts down the module when the maximum device  
reference temperature is exceeded. The module will  
automatically restart once the reference temperature cools  
by ~25°C.  
A factory configured auto-restart option (with overcurrent  
and overvoltage auto-restart managed as a group) is also  
available. An auto-restart feature continually attempts to  
restore the operation until fault condition is cleared.  
Remote On/Off  
Input Under/Over voltage Lockout  
The module contains a standard on/off control circuit  
reference to the VIN(-) terminal. Two factory configured  
remote on/off logic options are available. Positive logic  
remote on/off turns the module on during a logic-high  
voltage on the ON/OFF pin, and off during a logic low.  
Negative logic remote on/off turns the module off during a  
logic high, and on during a logic low. Negative logic, device  
code suffix "1," is the factory-preferred configuration. The  
On/Off circuit is powered from an internal bias supply,  
derived from the input voltage terminals. To turn the power  
module on and off, the user must supply a switch to control  
the voltage between the On/Off terminal and the VIN(-)  
terminal (Von/off). The switch can be an open collector or  
equivalent (see Figure 15). A logic low is Von/off = -0.3V to  
0.8V. The typical Ion/off during a logic low (Vin=48V, On/Off  
Terminal=0.3V) is 147µA. The switch should maintain a  
logic-low voltage while sinking 310µA. During a logic high,  
the maximum Von/off generated by the power module is  
8.2V. The maximum allowable leakage current of the  
switch at Von/off = 2.0V is 10µA. If using an external voltage  
source, the maximum voltage Von/off on the pin is 14.5V  
with respect to the VIN(-) terminal.  
At input voltages above or below the input under/over  
voltage lockout limits, module operation is disabled. The  
module will begin to operate when the input voltage level  
changes to within the under and overvoltage lockout limits.  
Load Sharing  
For higher power requirements, the EBVW025A0 power  
module offers an optional feature for parallel operation (-P  
Option code). This feature provides a precise forced output  
voltage load regulation droop characteristic. The output set  
point and droop slope are factory calibrated to insure  
optimum matching of multiple modules’ load regulation  
characteristics. To implement load sharing, the following  
requirements should be followed:  
.The VOUT(+) and VOUT(-) pins of all parallel modules must  
be connected together. Balance the trace resistance for  
each module’s path to the output power planes, to insure  
best load sharing and operating temperature balance.  
VIN must remain between 40Vdc and 75Vdc for droop  
sharing to be functional.  
.
.
It is permissible to use a common Remote On/Off signal  
to start all modules in parallel.  
If not using the remote on/off feature, perform one of the  
following to turn the unit on:  
. These modules contain means to block reverse current  
flow upon start-up, when output voltage is present from  
other parallel modules, thus eliminating the requirement  
for external output ORing devices. Modules with the –P  
option will self determine the presence of voltage on the  
output from other operating modules, and automatically  
increase its Turn On delay, Tdelay, as specified in the  
Feature Specifications Table.  
For negative logic, short ON/OFF pin to VIN(-).  
For positive logic: leave ON/OFF pin open.  
When parallel modules startup into a pre-biased output,  
e.g. partially discharged output capacitance, the Trise is  
automatically increased, as specified in the  
Feature Specifications Table, to insure graceful startup.  
. Insure that the load is <50% IO,MAX (for a single module)  
until all parallel modules have started (load full start >  
module Tdelay time max + Trise time).  
. If fault tolerance is desired in parallel applications, output  
ORing devices should be used to prevent a single  
module failure from collapsing the load bus.  
Figure 15. Remote On/Off Implementation.  
Output Overvoltage Protection  
The module contains circuitry to detect and respond to  
output overvoltage conditions. If the overvoltage condition  
LINEAGE POWER  
8