Data Sheet  
GE  
CP2725AC54TE CPL High Efficiency Rectifier  
100-120/200-277VAC input; Default Outputs: ±54VDC @ 2725W, 5VDC @ 4W  
Using the PCA9541 multiplexer: Transition between the two  
Status Signals  
I2C lines is provided by the industry standard PCA9541 I2C  
master selector multiplexer. Option 01 of the device code is  
supplied which, upon start-up, connects channel 0 to the  
power supply. In this fashion applications using only a single  
I2C line can immediately start talking across the bus without  
first requiring to reconfigure the multiplexer.  
Power Capacity: A HI on this pin indicates that the rectifier  
delivers high line rated output power; a LO indicates that the  
rectifier is connected to low line configured for 1200W  
operation.  
Power Fail Warning: This signal is HI when the main output is  
being delivered and goes LO for the duration listed in this data  
sheet prior to the output decaying below the listed voltage  
level.  
Fault: This signal goes LO for any failure that requires rectifier  
replacement. These faults may be due to:  
Fan failure  
Over-temperature warning  
Over-temperature shutdown  
Over-voltage shutdown  
Internal Rectifier Fault  
Figure 14. Diagram showing conceptual representation  
of the dual I2C bus system.  
Digital Feature Descriptions  
PMBus™ compliance: The power supply is fully compliant to  
the Power Management Bus (PMBus™) rev1.2 requirements  
with the following exceptions:  
Control can be taken over at any time by a specific ‘master’  
even during data transmission to the other ‘master’. The  
‘master’ needs to be able to handle incomplete transmissions  
in the multi-master environment in case switching should  
commence in the middle of data transmission.  
The power supply continuously updates its STATUS and ALARM  
registers to the latest state in order to capture the ‘present’  
state of the power supply. There are a number of indicators,  
such as those indicating a communications fault (PEC error,  
data error) that do not get cleared until specifically instructed  
by the host controller sending a clear_faults command. A ‘bit’  
indicator notifies the user if the STATUS and ALARM registers  
changed since the last ‘read’ by the host controller.  
Master/Slave: The ‘host controller’ is always the MASTER.  
Power supplies are always SLAVES. SLAVES cannot initiate  
communications or toggle the Clock. SLAVES also must  
respond expeditiously at the command of the MASTER as  
required by the clock pulses generated by the MASTER.  
Clock stretching: The ‘slave’ µController inside the power  
supply may initiate clock stretching if it is busy and it desires to  
delay the initiation of any further communications. During the  
clock stretch the ‘slave’ may keep the clock LO until it is ready  
to receive further instructions from the host controller. The  
maximum clock stretch interval is 25ms.  
For example, if a voltage surge causes a momentary shutdown  
for over voltage the power supply will automatically restart if  
the ‘auto_restart’ feature is invoked. During the momentary  
shutdown the power supply issues an Alert# indicating to the  
system controller that a status change has occurred. If the  
system controller reads back the STATUS and ALARM registers  
while the power supply is shut down it will get the correct fault  
condition. However, inquiry of the state of the power supply  
after the restart event would indicate that the power supply is  
functioning correctly. The STATUS and ALARM indicators did  
not freeze at the original shutdown state and so the reason for  
the original Alert# is erased. The restart ‘bit’ would be set to  
indicate that an event has occurred.  
The host controller needs to recognize this clock stretching,  
and refrain from issuing the next clock signal, until the clock  
line is released, or it needs to delay the next clock pulse  
beyond the clock stretch interval of the power supply.  
Note that clock stretching can only be performed after  
completion of transmission of the 9th ACK bit, the exception  
being the START command.  
The power supply also clears the STATUS and ALARM registers  
after a successful read back of the information in these  
registers, with the exception of communications error alarms.  
This automated process improves communications efficiency  
since the host controller does not have to issue another  
clear_faults command to clear these registers.  
Dual, redundant buses: Two independent I2C lines provide  
true communications bus redundancy and allow two  
independent controllers to sequentially control the power  
supply. For example, a short or an open connection in one of  
the I2C lines does not affect communications capability on the  
other I2C line. Failure of a ‘master’ controller does not affect the  
power supplies and the second ‘master’ can take over control  
at any time.  
Clock  
Stretch  
Figure 14. Example waveforms showing clock stretching.  
Communications speed: Both 100kHz and 400kHz clock rates  
are supported. The power supplies default to the 100kHz clock  
rate.  
January 30, 2014  
©2013 General Electric Company. All rights reserved.  
Page 10