Data Sheet  
GE  
CP2725AC54TE CPL High Efficiency Rectifier  
100-120/200-277VAC input; Default Outputs: ±54VDC @ 2725W, 5VDC @ 4W  
bit. To be certain that each power supply responded to the  
global instruction, a READ instruction should be executed to  
each power supply to verify that the command properly  
executed. The GLOBAL BROADCAST command should only be  
executed for write instructions to slave devices.  
data value from the controller and x is the ‘real’ value either  
being set or returned.  
For example, to set the output voltage to 50.45VDC, Multiply the  
desired set point by the m constant, 50.45 x 400 = 20,180.  
Convert this binary number to its hex equivalent: 20,180b =  
0x4ED4. The result is sent LSB=0xD4 first, then MSB=0x4E.  
Note: The PCA9541 i2c master selector does not respond to the  
GLOBAL BROADCAST command.  
The constants are  
Read back delay: The power supply issues the SMBAlert #  
notification as soon as the first state change occurred. During  
an event a number of different states can be transitioned to  
before the final event occurs. If a read back is implemented  
rapidly by the host a successive SMBAlert# could be triggered  
by the transitioning state of the power supply. In order to avoid  
successive SMBAlert# s and read back and also to avoid  
reading a transitioning state, it is prudent to wait more than 2  
seconds after the receipt of an SMBAlert# before executing a  
read back. This delay will ensure that only the final state of the  
power supply is captured.  
FUNCTION  
Output voltage  
Output voltage shutdown  
Output Current  
Temperature  
Input Voltage  
Input Power  
Fan Speed setting ( % )  
Fan speed in RPM  
Operation  
Write / read  
m
400  
b
0
R
0
read  
read  
read  
read  
read  
read  
5
1
1
1
1
0
0
75  
0
0
0
0
0
0
0
0
0
100  
PMBusTM Command set:  
Command  
Successive read backs: Successive read backs to the power  
supply should not be attempted at intervals faster than every  
one second. This time interval is sufficient for the internal  
processors to update their data base so that successive reads  
provide fresh data.  
Hex  
Code  
Data  
Field  
Function  
Operation  
Clear_Faults  
Vout_command  
Vout_OV_fault_limit  
Read_status  
LEDs test ON  
LEDs test OFF  
Service_LED_ON  
Service_LED_OFF  
Enable_write  
01  
03  
21  
40  
D0  
D2  
D3  
D4  
D5  
D6  
D7  
D8  
D9  
DA  
DC  
DD  
DE  
DF  
E0  
1
0
2
2
10  
0
0
0
0
0
0
0
0
0
2
3
3
Output ON/OFF  
Clear Status  
Set Vout  
Set OV fault limit  
Read Status, Vout, Iout, T  
Test LEDs  
Device ID: Address bits A2, A1, A0 set the specific address of  
the power supply. The least significant bit x (LSB) of the address  
byte configures write [0] or read [1] events. In a write  
command the system instructs the power supply. In a read  
command information is being accessed from the power  
supply.  
Service LED  
Enable EEPROM write  
Disable EEPROM write  
Latch upon failure  
Hiccup  
Perform isolation test  
Read Vin and Pin  
Firmware revisions  
Accumulated ON state  
Fan speed control  
Stop fan control  
Fan control & speed  
Production test feature  
Disable_write  
Inhibit_restart  
Auto_restart  
Address Bit  
7
1
1
1
0
6
1
0
0
0
5
1
0
1
0
4
0
0
0
0
3
2
1
0
PCA9541  
A2 A1 A0 R/W  
A2 A1 A0 R/W  
A2 A1 A0 R/W  
Isolation_test  
Micro controller  
External EEPROM  
Global Broadcast  
Read_input_string  
Read_firmware_rev  
Read_run_timer  
Fan_speed_set  
Fan_normal_speed  
Read_fan_speed  
Stretch_LO_25ms  
0
0
0
0
MSB  
LSB  
3
0
4
0
E1  
E2  
The Global Broadcast instruction executes a simultaneous  
write instruction to all power supplies. A read instruction  
cannot be accessed globally. The three programmable address  
bits are the same for all I2C accessible devices within the  
power supply.  
Command Descriptions  
Operation (01h) : By default the Power supply is turned ON at  
power up as long as ENABLE is active LO. The Operation  
command is used to turn the Power Supply ON or OFF via the  
PMBus. The data byte below follows the OPERATION command.  
PMBusTM Commands  
Standard instruction: Up to two bytes of data may follow an  
instruction depending on the required data content. Analog  
data is always transmitted as LSB followed by MSB. PEC is  
mandatory and includes the address and data fields.  
FUNCTION  
Unit ON  
Unit OFF  
DATA BYTE  
0x80  
0x00  
1
S
8
1
A
8
1
A
Slave address  
Wr  
Command Code  
To RESET the power supply cycle the power supply OFF, wait at  
least 2 seconds, and then turn back ON. All alarms and  
shutdowns are cleared during a restart.  
8
1
A
8
1
A
8
PEC  
1
A
1
P
Low data byte  
High data byte  
Clear_faults (03h): This command clears information bits in  
the STATUS registers, these include:  
Master to Slave  
Slave to Master  
SMBUS annotations; S – Start , Wr – Write, Sr – re-Start, Rd – Read,  
A – Acknowledge, NA – not-acknowledged, P – Stop  
Isolation OK  
Isolation test failed  
Restarted OK  
Direct mode data format: The Direct Mode data format is  
supported, where y = [ mX + b ] x 10R . In the equation, y is the  
Invalid command  
January 30, 2014  
©2013 General Electric Company. All rights reserved.  
Page 12