欢迎访问ic37.com |
会员登录 免费注册
发布采购

CP2000AC54PE 参数 Datasheet PDF下载

CP2000AC54PE图片预览
型号: CP2000AC54PE
PDF下载: 下载PDF文件 查看货源
内容描述: 紧凑型电源线输入: 100-120 / 200-240伏交流;输出: ± 54伏在2000W ; 5 VDC在4W [Compact Power Line Input: 100-120/200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W]
分类和应用:
文件页数/大小: 8 页 / 264 K
品牌: LINEAGEPOWER [ LINEAGE POWER CORPORATION ]
 浏览型号CP2000AC54PE的Datasheet PDF文件第1页浏览型号CP2000AC54PE的Datasheet PDF文件第2页浏览型号CP2000AC54PE的Datasheet PDF文件第3页浏览型号CP2000AC54PE的Datasheet PDF文件第5页浏览型号CP2000AC54PE的Datasheet PDF文件第6页浏览型号CP2000AC54PE的Datasheet PDF文件第7页浏览型号CP2000AC54PE的Datasheet PDF文件第8页  
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications (continued)
Environmental
Parameter
Ambient Temperature
Operating
Ambient Derating
2
Power Derating
Storage Temperature
Humidity
Shock and Vibration
Operational Test
Test Levels
Drop and Tip Over
Earthquake Rating
Acoustic Noise
Harmonic Emissions
Radiated Emissions
4
Min
-5
1
Typ
Max
45
Units
°C
°C
%/°C
%/°C
°C
%
Notes
Air inlet from sea level to 5,000 feet.
Per 1,000 feet above 5,000 feet.
Up to 55°C
From 55 to 75 °C
Relative humidity, non-condensing
IEC 68-2
IEC 721-3-2
IEC 68-2-31
1
1
2
-40
5
85
95
4
45
Per EN/IEC61000-3-2
dBA
Zone
Per Telcordia GR-63-CORE, all floors, when
installed in CP Shelf.
Noise is proportional to fan speed, load and
ambient temperature.
FCC and CISPR22 (EN55022) - Class B
FCC and CISPR22 (EN55022) Class B
Telcordia GR-1089-CORE - Class A
3
Conducted Emissions - ac
Conducted Emissions - dc
ESD
Radiated Immunity
Electrical Fast Transient Burst
Lightning Surge
Error Free
Damage Free
Conducted Immunity
Reliability (calculated)
Isolation
Input-Chassis/Signals
Input - Output
Output-Chassis/Signals
Service Life
Telcordia GR-1089-CORE and CISPR22 (EN55022) - Class A
Error free per EN/IEC 61000-4-2 Level 4 (8 kV contact discharge, 15 kV air discharge).
Error free per EN/IEC 61000-4-3 Level 3 (10 V/m).
Error free per EN/IEC 61000-4-4 Level 3 (2 kV, 5 kHz repetition rate)
EN/IEC61000-4-5 Level 4 (4 kV common mode, 2 kV differential mode).
ANSI C62.41 Level A3 (6 kV common and differential mode)
Error free per EN/IEC 61000-4-6 Level 3 (10Vrms).
400,000
Hours
At ambient of 25°C at full load per Telcordia SR-
332, Reliability Prediction for Electronic Equipment,
Method I Case III.
Per EN60950-1.
Consult factory for testing to this requirement
Per IEEE802.3.
25°C ambient, full load excluding fans.
1500
3000
2250
10
Vrms
Vrms
Vdc
Years
1. Designed to start at an ambient as low as -40°C, but may not meet operational limits until above -5°C.
2. Power derating shall consider only temperature variations at nominal line (100 – 120, 200 – 240Vrms). The unit may derate
faster if the input line is below nominal.
3. Class B radiated emmissions compliance requires the addition of a ferrite bead to each power line cord at the shelf-end of the
cable. See the figure below.
4. Radiated emissions compliance was met using a Lineage Power shelf. This shelf includes output common and differential mode
capacitors that assist in meeting compliance.
Lineage Power
4