Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A
Environmental Specifications
Parameter
Ambient Temperature
Min
-10
-40
Typ
Max
70
Units
°C
Notes
Derated above 50C
Storage Temperature
85
°C
Operating Altitude
2250/7382
8200/30k
2.5
m/ft
m / ft
%/°C
Non-operating Altitude
Power Derating with Temperature
Power Derating with Altitude
50C to 70C
2.0
Above 2250 m/7382 ft
C/301 m
C/1000 ft
Acoustic noise
55
45
Full load
Half load
dbA
°C
Over Temperature Protection
125/110
Shutdown / restart
Humidity
Operating
Storage
30
10
95
95
%
Relative humidity, non-condensing
Shock and Vibration
Meet IPC 9592 Class II, Section 5 requirements
EMC Compliance
Parameter
Function
Conducted
Standard
Level
Criteria
Test
EN55022, FCC part 15
EN61000-3-2
A*
0.15 – 30MHz
0 – 2 KHz
emissions
AC input
Radiated
EN55022
A*
30 – 10000MHz
emissions**
Voltage dips
EN61000-4-11
A
B
B
A
A
A
-30%, 10ms
-60%, 100ms
-100%, 5sec
AC input
immunity
Voltage surge
Fast transients
EN61000-4-5
EN61000-4-4
EN61000-4-6
4kV, 1.2/50µs, common mode
2kV, 1.2/50µs, differential mode
5/50ns, 2kV (common mode)
Conducted RF
fields
A
130dBµV, 0.15-80MHz, 80% AM
10V/m, 80-1000MHz, 80% AM
Enclosure
immunity
Radiated RF fields
EN61000-4-3
ENV 50140
A
A
B
ESD
EN61000-4-2
4kV contact, 8kV air
* Note: Contact the factory for a recommended external EMI filter to meet Class B emissions
** Radiated emissions compliance is contingent upon the final system configuration.
Criteria
Performance
A
B
C
D
No performance degradation
Temporary loss of function or degradation not requiring manual intervention
Temporary loss of function or degradation that may require manual intervention
Loss of function with possible permanent damage