 浏览型号CAR0812DCBXXZ01A的Datasheet PDF文件第8页浏览型号CAR0812DCBXXZ01A的Datasheet PDF文件第9页浏览型号CAR0812DCBXXZ01A的Datasheet PDF文件第10页浏览型号CAR0812DCBXXZ01A的Datasheet PDF文件第11页浏览型号CAR0812DCBXXZ01A的Datasheet PDF文件第12页浏览型号CAR0812DCBXXZ01A的Datasheet PDF文件第13页浏览型号CAR0812DCBXXZ01A的Datasheet PDF文件第15页浏览型号CAR0812DCBXXZ01A的Datasheet PDF文件第16页  
Data Sheet  
GE  
CAR0812DC Series DC-DC Converter  
Input: -36VDC to -75VDC; Output: +12 VDC @ 850W; 3.3VDC or 5 VDC @ 1A  
Status_word (79): returns two bytes of information. The upper  
EEPROM  
byte bit functionality is tabulated in the Status_word section.  
The lower byte bit functionality is identical to Status_byte.  
The microcontroller has 96 bytes of EEPROM memory available  
for the system host.  
Fan_speed (D7): This register can be used to ‘read’ the fan  
speed in adjustment percent (0 – 100%) or set the fan speed in  
adjustment percent (0 – 100%). The speed of the fan cannot  
be reduced below what the power supply requires for its  
operation. The register value is the percent number, it is not in  
linear format.  
A separate EEPROM IC, with write protect features, provides  
another 128 bytes of memory. Minimum information to be  
included in this separate EEPROM: model number, revision,  
date code, serial number etc.  
Invalid commands or data: The power supply notifies the  
MASTER if a non-supported command has been sent or invalid  
data has been received. Notification is implemented by setting  
the appropriate STATUS and ALARM registers and setting the  
SMBAlert# flag.  
LEDs  
Two LEDs are located on the front faceplate. The INPUT OK LED  
provides visual indication of the INPUT signal function. When  
the LED is ON GREEN the power supply input is within normal  
design limits.  
Control and Read accuracy:  
The second LED DC/FLT provides visual indication of three  
different states of the power supply. When the LED is GREEN  
then there are no faults and the DC output is present. When  
the LED is AMBER then a fault condition exists but the power  
supply still provides output power. When the LED is RED then a  
fault condition exists and the power supply does not provide  
output power.  
The estimates below are believed to be reasonable under most  
operating conditions. However, these are typical numbers and  
not hard bound values that cannot be exceeded. In most  
nominal operating conditions the returned values are  
significantly better than these estimates.  
FUNCTION  
ACCURACY  
± 2%  
Vout_command  
Vout_OV_fault_limit  
Iout_OC_warn_limit  
OT_warn_limit  
Vin_UV_warn_limit  
Vin_UV_fault_limit  
Read_Vin  
± 3%  
± 4% of FL  
± 5C  
± 3%  
± 3%  
± 3%  
± 2%  
Read_Vout  
± 4% of FL  
Read_Iout  
± 5C  
Read_temperature  
Alarm/LED indicator Table  
LED Indicator  
Monitoring Signals  
LED1  
Tri-Color LED2  
Test Condition  
Normal Operation  
Low or NO INPUT  
OVP  
INPUT OK  
Green  
Off  
DC OK  
Green  
Red  
FAULT  
High  
Low  
DC OK  
High  
Low  
INPUT OK  
High  
TEMP OK  
High  
High  
High  
High  
Low  
1
2
3
4
5
6
7
Low  
Green  
Green  
Green  
Green  
Green  
Red  
Low  
Low  
High  
Red  
Over Current  
Low  
Low  
High  
Orange  
Red  
Temp Alarm Warning  
Fault Over Temp  
Remote ON/OFF  
High  
Low  
High  
Low  
High  
High  
Low  
Red  
Low  
Low  
High  
High  
Note: Test condition #2 had 2 modules plug in. One module is running and the other one is with no Input.  
April 23, 2013  
©2013 General Electric Company. All rights reserved.  
Page 14  