Current Transducer LTS 6-NP
Isolation characteristics
Vd
VW
Rms voltage for AC isolation test, 50 Hz, 1 min
Impulse withstand voltage 1.2/50 µs
3
> 8
kV
kV
Mini
Ve
Rms voltage for partial discharge extinction @ 10pC
> 1.5
kV
Mini
15.5
6.35
175
5)
dCp
dCl
CTI
Creepage distance
Clearance distance
m m
m m
6)
Comparative Tracking Index (Group III a)
Applicationexamples
According to EN 50178 and IEC 61010-1 standards and following conditions:
· Over voltage category OV 3
· Pollution degree PD2
· Non-uniform field
EN 50178
Rated isolation voltage
600 V
IEC 61010-1
Nominal voltage
600 V
dCp, dCI,
VW
Single isolation
Reinforced isolation
300 V
300 V
5)
Notes:
On housing
On PCB with soldering pattern UTEC93-703.
6)
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer's
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.