Current Transducer HAL 200-S
For the electronic measurement of DC, AC and pulsed currents,
with a galvanic isolation between the primary (high power) circuit
and the secondary (electronic) circuit.
I
PN
= 200 A
Electrical data
I
PN
I
P
Î
P
V
OUT
R
L
V
C
I
C
V
b
V
d
R
is
Primary nominal DC or rms current
Primary current, measuring range
Overload capacity (Ampere Turns)
Analogue output voltage @ ±
I
PN
Load resistance
T
A
= 0 .. + 70°C
T
A
= - 25 .. + 85°C
Supply voltage (± 5 %)
Current consumption (max)
Rms rated voltage
1)
Rms voltage for AC isolation test, 50 Hz, 1 mn
Isolation resistance @ 500 V
DC
200
0 .. ± 600
30000
±4
>1
>3
± 15
25
500
3
> 500
A
A
A
V
kΩ
kΩ
V
mA
V
kV
MΩ
Features
•
Open loop transducer using Hall
Effect
•
Panel mounting - Horizontal or
Vertical
•
Insulated plastic case to UL 94-V0.
Advantages
•
•
•
•
•
•
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external
interference
•
Current overload capability
•
Low power consumption
•
Wide dynamic range, 50 to 600 A in
one package.
Accuracy - Dynamic performance data
ε
X
L
Accuracy
2)
@
I
PN
,
T
A
= 25°C, @ ± 15 V
Linearity
2)
Electrical offset voltage @
I
P
= 0,
T
A
= 25°C
Residual offset voltage @
I
P
= 0
after an overload of 3 x
I
PN
Thermal drift of offset voltage
T
A
= - 25 .. + 85°C
Thermal drift of gain
T
A
= - 25 .. + 85°C
Response time @ 90 % of
I
P
di/dt accurately followed
Frequency bandwidth (- 3 dB)
3)
V
OE
V
OM
V
OT
TC
ε
G
t
r
di/dt
f
±1
± 0.5
Max
± 10
± 10
±1
± 0.05
<3
> 50
DC .. 50
%
%
mV
mV
mV/°K
%/°K
µs
A/µs
kHz
Applications
•
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptable Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards Safety
EMC
Deviation in output when tested to EN 61000-4-6
Deviation in output when tested to EN 61000-4-4
- 25 .. + 85
°C
- 25 .. + 85
°C
75
g
EN50178 (1994)
EN50082-2 (1992)
EN50081-1 (1992)
< 10
% of
I
PN
< 10
% of
I
PN
•
•
•
•
•
Notes :
1)
2)
3)
Reinforced insulation, Overvoltage Category II, Pollution Degree 2
Excludes the electrical offset
Refer to derating curves in the technical file to avoid excessive core
heating at high frequency
001114/2
LEM Components