Current Transducers HAC 100 ... 800-S
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
I
PN
= 100 .. 800 A
Preliminary
Electrical data
Primary nominal
r.m.s. current
I
PN
(A)
100
200
300
400
600
800
Primary current
measuring range
I
P
(A)
± 300
± 600
± 900
± 900
± 1800
± 1800
Type
HAC 100-S
HAC 200-S
HAC 300-S
HAC 400-S
HAC 600-S
HAC 800-S
Features
Hall effect measuring principle
Galvanic isolation between primary
V
mA
mA
kV
MΩ
V
kΩ
and secondary circuit
Isolation voltage 2500 V
Low power consumption
Extended measuring range (3 x
I
PN
)
V
C
I
C
V
d
R
IS
V
OUT
R
OUT
R
L
± 15
HAC 100-S .. 400-S
< ± 18
HAC 600-S .. 800-S
< ± 25
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn 2.5
Isolation resistance @ 500 VDC
> 1000
Output voltage @ ±
I
PN
,
R
L
= 10 kΩ,
T
A
= 25°C
±4
Output internal resistance
100
Load resistance
>10
Supply voltage (± 5 %)
Current consumption
Advantages
Easy mounting
Small size and space saving
Only one design for wide current
ratings range
High immunity to external
interference.
Accuracy - Dynamic performance data
X
ε
L
V
OE
V
OH
V
OT
TC
ε
G
t
r
f
Accuracy @
I
PN
,
T
A
= 25°C (without offset)
Linearity (0 .. ±
I
PN
)
Electrical offset voltage,
T
A
= 25°C
Hysteresis offset voltage @
I
P
= 0;
after an excursion of 1 x
I
PN
Thermal drift of
V
OE
Thermal drift (% of reading)
Response time @ 90% of
I
P
Frequency bandwidth (- 3 dB)
1)
< ± 1 % of
I
PN
< ± 1 % of
I
PN
< ± 30
mV
< ± 35
<±1
< ± 0.1
<7
DC .. 50
mV
mV/K
%/K
µs
kHz
Applications
AC variable speed drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
(UPS)
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass
- 10 .. + 80
- 15 .. + 85
70
°C
°C
g
Notes : EN50178 approval pending
1)
Derating is needed to avoid excessive core heating at high frequency.
010118/2
LEM Components
www.lem.com