AC/DC Current transducer DHR-C420 IPN = 100..1000 A  
The transducer for the electronic measurement of DC & distorted AC  
waveform currents, with galvanic isolation between the primary circuit  
(power) and the secondary circuit (measurement). True RMS 4-20mA  
current output.  
Features  
Electrical data  
· VFD and SCR waveforms current  
measurement  
PrimaryNominal  
DC & AC Current  
IPN (A.t.RMS)  
Primary AC Current  
Max. Peak Value (*)  
IP (A)  
Output current  
IOUT (mADC)  
Type  
· True RMS output  
· 4-20mA current output  
· Panel mounting  
100  
200  
300  
400  
500  
600  
1000  
600  
600  
4-20  
4-20  
4-20  
4-20  
4-20  
4-20  
4-20  
DHR 100 C420  
DHR 200 C420  
DHR 300 C420  
DHR 400 C420  
DHR 500 C420  
DHR 600 C420  
DHR 1000 C420  
· Eliminates insertion loss  
· Insulated plastic case recognized  
according to UL94-V0  
1000  
1000  
1800  
1800  
1800  
Advantages  
RL  
VC  
IC  
ISL  
ÎP  
Load resistance  
Supply voltage  
Current consumption  
Output current limitation  
Overload capability (Ampere Turns)  
< 300  
+ 20 .. 50 V DC  
30 mA + IOUT  
< 25  
W
· Large aperture for cable up to  
Ø32mm  
mA  
A.t  
· High isolation between primary and  
secondary circuits  
30000  
· Easy installation  
Performance data  
X
Accuracy @ IPN, TA = 25°C (excluding offset)  
Linearity error (1% of IPN .. ± IPN)  
Electrical offset current, TA = 25°C  
Temperature coefficient of IOE ( 0..+60 °C)  
(-40..+70 °C)  
Temperature coefficient of IOUT (% of reading)  
Response time to 90% of IPN step  
Frequency bandwidth (±1dB)  
< ± 1 % of IPN  
< ± 1.0 % of IPN  
Applications  
e
L
IOE  
4
mA  
mA/K  
mA/K  
%/K  
m s  
· VFD Controlled Loads  
TCIOE  
± 3.2  
± 6.4  
± 0.1  
< 150  
VFD output indicates how the motor  
and attached load are operating.  
· SCR Controlled Loads  
TCIOUT  
tr  
BW  
Acurate measurement of phase  
angle fired or burst fired (time  
proportioned)  
DC 20..6000Hz  
General data  
SCRs. Current measurement gives  
faster response than temperature  
measurement.  
TA  
TS  
m
Ambient operating temperature  
Ambient storage temperature  
Mass  
- 40 .. + 70 °C  
- 40 .. + 85 °C  
260  
g
· Switching Power Supplies and  
Electronic Ballasts  
IPxx  
Protection degree  
IP20  
True RMS sensing is the most  
accurate way to measure power  
supply or ballast input power.  
Note : (*) The Max. Peak AC Current is the highest peak level of the primary signal that is  
taken into account for accurate True RMS calculation. Yet the device is designed for  
maximum continuous True RMS value equal to IPN, whereas the output is limited by  
the above specified output limitation.  