Dimensions CT 100-S
Front view
(in mm. 1 mm = 0.0394 inch)
Left view
Secondary terminals
Terminal
Terminal
Terminal
Terminal
+
M
0
-
:
:
:
:
supply voltage + 15 V
measure
0V
supply voltage - 15 V
Connection
Top view
Mechanical characteristics
•
•
•
•
General tolerance
Fastening
Primary through-hole
Connection of secondary
Fastening torque
± 0.3 mm
2 x M5 screws
∅
15 mm
M5 threaded studs
2.2 Nm or 1.62 Lb - Ft
Remarks
•
V
OUT
is positive when
I
P
flows in the direction of the arrow.
•
This transducer induces into the primary circuit a square
wave of 3.5 mV amplitude (frequency
≈
220 Hz). This voltage
can induce an AC current in the primary if the primary
impedance is low.
•
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.