Digital Field Bus  
Communication  
Networks  
To date, despite its many draw-  
backs, the 4 - 20 mA analog  
current loop has been the most  
widely accepted standard for  
implementing process control  
systems. In today’s manufacturing  
environment, however, automated  
systems are expected to help  
manage the process, not merely  
monitor it. With the advent of  
digital field bus communication  
networks such as DeviceNet,  
PROFIBUS, and Smart Distributed  
Systems (SDS), gone are the days  
of constrained information.  
Controllers can now receive  
multiple readings from field  
devices (sensors, actuators, etc.)  
in addition to diagnostic  
The physical model for each of  
these digital field bus communica-  
tion networks is very similar as  
shown in Figure 16. Each  
includes one or more buses, an  
interface unit, optical isolation,  
transceiver, and sensing and/or  
actuating devices.  
information.  
CONTROLLER  
BUS  
INTERFACE  
OPTICAL  
ISOLATION  
TRANSCEIVER  
FIELD BUS  
TRANSCEIVER  
TRANSCEIVER  
TRANSCEIVER  
TRANSCEIVER  
OPTICAL  
ISOLATION  
OPTICAL  
ISOLATION  
OPTICAL  
ISOLATION  
OPTICAL  
ISOLATION  
BUS  
INTERFACE  
BUS  
INTERFACE  
BUS  
INTERFACE  
BUS  
INTERFACE  
XXXXXX  
YYY  
SENSOR  
DEVICE  
CONFIGURATION  
MOTOR  
CONTROLLER  
MOTOR  
STARTER  
Figure 16. Typical Field Bus Communication Physical Model.  
the network is used only for the  
transceiver and input (network)  
side of the optocouplers.  
false signals. In addition, the  
network receives maximum  
protection from power system  
faults and ground loops.  
Optical Isolation for  
Field Bus Networks  
To recognize the full benefits of  
these networks, each recom-  
mends providing galvanic  
isolation using Hewlett-Packard  
optocouplers. Since network  
communication is bi-directional  
(involving receiving data from  
and transmitting data onto the  
network), two Hewlett-Packard  
optocouplers are needed. By  
providing galvanic isolation, data  
integrity is retained via noise  
reduction and the elimination of  
Isolation of nodes connected to  
any of the three types of digital  
field bus networks is best  
Within an isolated node, such as  
the DeviceNet Node shown in  
Figure 17, some of the node’s  
components are referenced to a  
ground other than V- of the  
network. These components could  
include such things as devices  
with serial ports, parallel ports,  
RS232 and RS485 type ports. As  
shown in Figure 17, power from  
achieved by using the HCPL-0710  
optocoupler. For each network,  
the HCPL-0710 satisifies the  
critical propagation delay and  
pulse width distortion require-  
ments over the temperature range  
of 0°C to +85°C, and power  
supply voltage range of 4.5 V  
to 5.5 V.