MOUNTING  
· On a 4-inch square box with or without  
plaster ring or supplied adapter. Minimum  
depth 1.5 inches.  
· On a 3 1/2 or 4-inch octagonal box. Minimum  
depth 1.5 inches.  
VIEWS SHOWING POSITION OF TEST MAGNET  
· On a single gang box. Min. depth 1.5 inches.  
INSTALLATION  
Place the detector into the detector base. Turn the de-  
tector clockwise until the detector locks into place.  
To use the tamper-proof feature, break the smaller tab  
on the scribed line in the tamper proof tab located on the  
detector mounting bracket. Install the detector. To re-  
move the detector from the base when using the tam-  
per-proof feature, insert the blade of a small  
screwdriver into the hole on the side of the base and  
push the plastic lever away from the detector head. This  
will allow the detector to be rotated counterclockwise  
for removal. NOTE: The decorative ring must be re-  
moved in order to remove the head when using the tam-  
per-proof feature.  
WARNING: To prevent detector contamination  
during construction, smoke detectors must be  
protected from dust and contamination until area  
is clean and dust free. See NFPA 72-5-3.7.1.3.  
The tamper-proof feature may be defeated perma-  
nently by breaking the plastic lever off the base.  
NOTE: The number of two-wire smoke detectors  
which can be accommodated per zone varies with dif-  
ferent control panels. Consult the control panel in-  
struction manual to determine the capacity.  
Refer to NFPA 72, Chapter 5-3 “Smoke Sensing Fire  
Detectors” for spacing, location of detectors and other  
guidelines.  
· Field metering of detector sensitivity may be  
performed with the aid of a voltmeter and Test  
Kit MOD 400R.  
For the complete procedure, refer to the Installation  
and Maintenance instructions furnished with each de-  
tector.  
TESTING  
Detectors may be tested in the following ways:  
· Place a test magnet against the cover opposite  
the test module socket (See illustration above).  
The detector should go into alarm within 5 sec-  
onds.  
MAINTENANCE  
Cleaning programs should be adapted to the individ-  
ual environment in conformance with NFPA Standard  
72. We recommend, at the least, an annual cleaning of  
the unit. The detector screen and cover assembly can be  
removed, revealing the sensing chamber. A vacuum  
cleaner can be used to remove dust from the screen,  
cover and sensing chamber. For the complete proce-  
dure, refer to the Installation and Maintenance instruc-  
tions furnished with each detector.  
· A test card with one end marked “ALARM”  
and the other end marked “NO ALARM” is fur-  
nished with each unit. For the complete proce-  
dure, refer to the Installation and Maintenance  
instructions furnished with each detector.  
ORDERING AND TECHNICAL INFORMATION  
Part No.  
Model  
Supv.  
Alarm  
Contacts  
Description  
Current  
Current  
2451  
2451T  
——  
——  
.00012 A  
.00012 A  
——  
——  
——  
Form A, C*  
Photoelectronic Detector  
Photo. Detector w/135oF thermal  
Base, two-wire  
B401B  
B402B  
301B4AC  
RA-400  
PAM-1  
.036 A  
Base, four-wire, 24 VDC operation  
Form A, C* & Supv. Base, four-wire, 120 VAC operation  
Remote Alarm Indicator  
Form B  
.007 A  
.015 A  
End of Line Relay, 24 VDC  
Test Kit  
* Resistive load (contact ratings):  
Form A - 2.0 A. @ 30 VAC/DC  
Form C - 2.0 A. @ 30 VAC/DC, 1.0A. @ 120 VAC  
NOTE: Alarm current of detector is limited by control panel initiating device circuit.  
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control  
Instruments, Inc. for their use. Specifications subject to change without notice.  
© 2003 All Rights Reserved  