WARNING: CONTACT COOPER-  
WHEELOCK FOR THE CURRENT IN-  
Engineer’s Specifications  
STALLATION  
INSTRUCTIONS  
(P83983) SERIES NS-24MCW, (P84234)  
SERIES NS-12 AND 24 VDC SINGLE  
CANDELA MODELS, (P83600) SERIES  
NH AND “GENERAL INFORMATION”  
SHEET (P82380) ON THESE PROD-  
UCTS. THESE DOCUMENTS UNDERGO  
PERIODIC CHANGES. IT IS IMPOR-  
TANT THAT YOU HAVE CURRENT IN-  
FORMATION ON THESE PRODUCTS.  
THESE MATERIALS CONTAIN IMPOR-  
TANT INFORMATION THAT SHOULD BE  
READ PRIOR TO SPECIFYING OR IN-  
STALLING THESE PRODUCTS, IN-  
CLUDING:  
The audible/visual notification appliances shall be Cooper-Wheelock Series NS Horn Strobe  
appliances and Series NH Horn appliances or approved equals. The Series NS appliances shall  
meet and be listed for ULStandard 1971(Emergency Devices for the Hearing-Impaired for Indoor  
Fire Protection Service). The Series NH Horn shall be UL Listed under Standard 464 (Fire  
Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the require-  
ments of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity  
supervision of circuit wiring by the FireAlarm Control Panel (FACP).  
The audible portion of the appliance shall have a minimum of two (2) field selectable settings for  
dBA levels (90 and 95 dBA) and shall have a choice of continuous or temporal (Code 3) audible  
outputs.  
The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over  
the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged  
Lexan lens. The Series NS shall be of low current design. Where wall mount, Multi-Candela  
appliances are specified, the strobe intensity shall have field selectable settings and shall be  
rated per UL Standard 1971 for 15/30/75/110 candela. The selector switch for selecting the  
candela setting shall be tamper resistant. The 15/75 candela strobe shall be specified when 15  
candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADAcompliance).  
TOTAL CURRENT REQUIRED BY ALL  
APPLIANCES CONNECTED TO SYSTEM  
SECONDARY POWER SOURCES.  
FUSE RATINGS ON NOTIFICATION AP-  
PLIANCE CIRCUITS TO HANDLE PEAK  
CURRENTS FROM ALL APPLIANCES  
ON THOSE CIRCUITS.  
When synchronization is required, the appliance shall be compatible with Cooper- Wheelock’s  
SM, DSM Sync Modules or a Power Supply with Cooper-Wheelock’s built-in Patented Sync  
Protocol. The strobes shall not drift out of synchronization at any time during operation. If the  
sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall  
revert to a non-synchronized flash-rate. The appliance shall also be designed so that the  
audible signal may be silenced while maintaining strobe activation.  
COMPOSITE FLASH RATE FROM MUL-  
TIPLE STROBES WITHINA PERSON’S  
FIELD OF VIEW.  
The Series NS Horn Strobes and NH horn shall incorporate a Patented Universal Mounting Plate  
that shall allow mounting to a single-gang, double-gang, 4-inch square, 100mm European type  
backboxes, or the SHBB Surface Backbox. If required, an NATP (NotificationAppliance Trimplate)  
shall be provided.  
ADDING, REPLACING OR CHANGINGAP-  
PLIANCES OR CHANGING CANDELA  
SETTINGS WILL AFFECT CURRENT  
DRAW.  
All notification appliances shall be backward compatible.  
RECALCULATE CURRENTDRAWTO IN-  
SURE THAT THE TOTAL AVERAGE  
CURRENTANDTOTALPEAK REQUIRED  
BYALLAPPLIANCES DO NOT EXCEED  
THE RATED CAPACITY OFTHE POWER  
SOURCES OR FUSES.  
Wiring Diagram  
NS/NH  
APPLIANCE  
TO NEXT  
APPLIANCE  
OR EOLR  
FROM  
PRECEDING  
APPLIANCE, SM/DSM,  
PS-12/24-8MP OR  
FACP  
+
+
-
-
THE VOLTAGE APPLIED TO THESE  
PRODUCTS MUST BE WITHIN THEIR  
“REGULATED VOLTAGE RANGE”.  
-
+
INSTALLATION OF 110 CANDELA  
STROBE PRODUCTS IN SLEEPINGAR-  
EAS.  
NS AND NH APPLIANCES SYNCHRONIZED  
WITH SM MODULE SINGLE CLASS “B”  
NAC CIRCUIT WITH AUDIBLE SILENCE  
FEATURE  
SM  
INSTALLATION IN OFFICEAREASAND  
OTHER SPECIFICATIONAND INSTALLA-  
TION ISSUES.  
+
STROBE  
F
A
C
P
-
STROBE  
Strobe  
NAC  
Circuit  
NS  
NH  
THESE APPLIANCES ARE NOT DE-  
SIGNED TO BE USED ON CODED SYS-  
TEMS IN WHICHTHEAPPLIED VOLTAGE  
IS CYCLED ONAND OFF.  
+
Audible  
EOLR  
-
Audible  
Audible  
NAC  
FAILURE TO COMPLYWITHTHE INSTAL-  
LATION INSTRUCTIONS OR GENERAL  
INFORMATION SHEETS COULD RESULT  
IN IMPROPER INSTALLATION,APPLICA-  
TION,AND/OR OPERATION OF THESE  
PRODUCTS INAN EMERGENCY SITUA-  
TION, WHICH COULD RESULT IN PROP-  
ERTY DAMAGE AND SERIOUS INJURY  
OR DEATH TO YOUAND/OR OTHERS.  
Circuit  
NS AND NH APPLIANCES SYNCHRONIZED  
WITH DSM MODULE DUAL CLASS “A”  
NAC CIRCUIT WITH NO AUDIBLE SILENCE  
FEATURE  
DUAL SYNC MODULE  
SYNC  
+
-
SYNC  
OUT1  
+
IN1  
+
MINUS1  
+
-
F
+
-
AUDIBLE  
AUDIBLE  
A
C
P
SIGNAL  
CIRCUIT OUT  
CONDUCTOR SIZE (AWG), LENGTH  
AND AMPACITY SHOULD BE TAKEN  
INTOCONSIDERATIONPRIORTODESIGN  
AND INSTALLATION OF THESE PROD-  
UCTS, PARTICULARLY IN RETROFIT IN-  
STALLATIONS.  
+
APPLIANCE  
-
+
APPLIANCE  
-
OUT2  
IN2  
+
+
+
-
MINUS2  
SIGNAL  
CIRCUIT RETURN  
NOTE: NS/NH must be set on Code 3 horn to achieve synchronized temporal (Code 3) tone.  
Refer to instruction (P38983, P83600 respectively).  
Page 2 of 3  
NS Series Horn Strobes & NH Series Horns CS-2246 09/01/06