Application Examples  
Temporal Coding on Multi-Alert and PA400  
(Non-SpectrAlert Horns)  
• Program module to provide temporal coding by inserting  
jumper plug per instructions.  
• Connect only sounders producing a continuous tone to  
the module zone output(s).  
Strobes cannot be used on a  
module providing temporal  
coding to horns! Strobes must be wired for inde-  
pendent operation.  
NOTE: Temporal jumper should be inserted across both pins  
only on non-SpectrAlert products that are to be powered for  
temporal sound output.  
Synchronize SpectrAlert Horns and Strobes  
This input powers the MDL Module. This input must have voltage present from the  
FACP before anything will work. This also supplies voltage to Zone 1 output.  
ZONE 1 INPUT  
This input only supplies voltage to Zone 2 output. NOTE: If Zone 1 input is not  
powered, the notification devices attached to the Zone 2 output will not be allowed.  
ZONE 2 INPUT  
This input enables the horns on the SpectrAlert notification appliances. Voltage  
present means horns are enabled. No voltage present means horns are disabled.  
HORN CONTROL  
SLAVE IN Connects to Master MDL Module slave out.  
SLAVE OUT Connects to Slave MDL slave in.  
Synchronize SpectrAlert  
Horns and Strobes  
• Each module can power two  
three-amp circuits wired in  
Class B, or one three-amp  
circuit powered as Class A.  
• Each module will synchronize  
two zones.  
• Additional modules can be  
added and may be synchro-  
nized to all other modules by  
interconnecting the “slave”  
input and output terminals  
between modules.  
Page 2 of 4  
MDL & MDLW Sync Modules CS-2456 10/21/04