Programming (Continued)  
Specifications (Continued)  
When the sensor head is inserted into the base, the  
address is automatically relayed to the sensor. Changing  
the sensor does not require additional programming since  
the address remains on the XPert card located in the base.  
All other sensor-specific programming is accomplished at  
the FACP.  
Relay Versions Only:  
Relay Contacts:  
Two dry Form-C contacts  
Relay Contact Ratings:10 A @ 24 VDC resistive  
maximum  
Operating Voltage:  
Current:  
24 VDC  
Standby current:  
0.010 A @ 24 VDC  
Alarm current:  
0.055 A @ 24 VDC  
Engineer’s Specifications  
The contractor shall furnish and install, where indicated on  
the plans, analog addressable air duct smoke detectors.  
The sensors shall be listed by Underwriter’s Laboratories  
per UL 268A and UL-Listed as compatible with the Fire  
Alarm Control Panel (FACP). The sensors shall operate at  
air velocities from 300 to 4,000 feet (91.44 to 1219.20 m) per  
minute. The smoke sensor shall contain an integral LED  
that shall latch in when the unit goes into alarm, mounted at  
a 30° slant to provide a wide viewing angle.  
Ordering Information  
Model  
Description  
XP95-ID  
Two-wire air duct, ionization smoke detector  
24 VDC (RW-AAN)  
XP95-PD Two-wire air duct, photoelectric smoke  
detector 24 VDC (RW-AAP)  
30203-01 Remote LED alarm indicator (two VDCs);  
used with XP95-PD and XP95-ID  
XP95-IDR Four-wire air duct, ionization smoke detector  
24 VDC with relay (RW-ARN)  
A manual reset/test switch shall be located on the front of  
the device. The housing shall contain a sensor base which  
will accept photoelectric or ionization heads. All wiring must  
comply with local codes and regulations. The duct sensor  
housing shall have a metal chassis with a clear plastic  
cover and complete mechanical installation may be per-  
formed without removal of the cover. The duct smoke  
detector shall be the Gamewell-FCI model, XP95-ID(R) or  
XP95-PD(R) analog addressable duct smoke detector.  
XP95-PDR Four-wire air duct, photoelectric smoke  
detector 24 VDC with relay (RW-ARP)  
Remote LED alarm indicator (24 VDCs);  
used with relay versions  
30203  
30007-02 Remote test station with alarm LED;  
used with relay versions  
70896-02 Sampling tube, 2.5 feet (0.762 m)  
70896-05 Sampling tube, 5 feet (1.524 m)  
70896-10 Sampling tube, 10 feet (3.048 m)  
Specifications  
XP95-I  
XP95-P  
72247  
Ionization sensor head (replacement)  
Photoelectric sensor head (replacement)  
Duct detector enclosure (WP-1)  
(See Data Sheet CS-2308).  
Ambient Temperature: 32° F to 120°F (0°C to 49°C)  
Humidity:  
Material:  
10% to 85% R.H  
18 gauge steel backbox,  
clear plastic cover  
Dimensions:  
10.0" H x 8.25" W x 2.25" D  
(25.4 H x 21.0 W x 5.7 D cm)  
Maximum Net Weight: 4.0 lbs. (1.814 kg)  
Mounting: Template and necessary  
hardware supplied  
Radioactive Element: For Ionization versions only:  
Americium 241 (0.9 microcuries)  
Sensitivity:  
Factory set (ion); or adjustable  
via the IF600 control panel  
(photoelectric)  
Air Velocity:  
300 to 4,000 feet per minute.  
Pressure Differential: 0.01 to 1.2 inches (1.524 to 20.320  
meters per second) of water  
Standby Current:  
Photoelectric: 340 µA  
Ionization: 280 µA  
Photoelectric: 4 mA  
Ionization: 2 mA  
Alarm LED Current:  
Remote Alarm Output  
Range:  
20 mA maximum; diode gated  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
CS-2049 Rev. a1 page 2 of 2  