Surge arrester
B88069X5691C103
A80-A800XP
2-electrode arrester
Features
Applications
AC power line devices – class II
Small size
Very fast response time
Stable performance over life
High insulation resistance
RoHS-compatible
Electrical specifications
DC spark-over voltage 1) 2)
> 600
V
V
Impulse spark-over voltage
- at 1.2/50 µs; 6 kV for 99 % of measured values
< 1500
Response time
< 100
< 20
ns
ns
- typical values
Insulation resistance at 100 Vdc
> 1
GΩ
Class II 3)
Max. continuous operating voltage at 50/60 Hz
Nominal discharge current 8/20 µs
Maximum discharge current 8/20 µs
Uc
In
Imax
255
10
20
Vrms
kA
kA
Weight
~ 2
g
Operation and storage temperature
Climatic category (IEC 60068-1)
Marking, blue positive
-40 ... +90
40/ 90/ 21
°C
800 YY O
800
YY
O
- Nominal voltage
- Year of production
- Non radioactive
1)
At delivery AQL 0.65 level II, DIN ISO 2859
In darkness w/o storage
Test sequence in accordance with EN 61643-11.
2)
3)
Application only in devices. Follow current has to be limited by an
appropriate varistor in series.
KB AB E / KB AB PM
Issue 04 / 2007-05-02
Please read Cautions and warnings and
Page 2 of 4
Important notes at the end of this document.