EXPLORA
EXP Series EXPlora - Hazardous Area Connector
SPECIFICATION
Electrical:
Mechanical:
No Poles:
2, 3, 4, 5
18A
7
10
10A
Sealing:
IP68, EN60529:2001 tested @
1.054kg/sq.cm. (15lb/sq.in.) 10m depth for
2 weeks
Current Rating:
16A
Voltage Rating:
600Vac/dc
430Vac/dc
250Vac/dc
Cable Acceptance:
EXP-0911 - EXP-0921 13 - 15mm O/D standard,
7-13mm with gland pack
EXP-A911 - EXP-A921 20 - 22mm O/D standard,
14 - 20mm with gland pack
Contact Resistance:
Insulation Resistance:
Dielectric strength:
AC Breakdown voltage:
Ambient Temperature Range:
Standards:
<10mΩ (initial)
6
>10 MΩ (@ 500V dc)
2
Contact Accommodation:
2.5 to 4mm (13 to10AWG) conductor,
2.2kV ac min
6kV
single or multi stranded
Termination:
Axial screw terminals
–20°C to +55°C
Cable Retention force:
22mm dia, 150N
15mm dia, 150N
7mm dia, 80N
ATEX Zone 2 and Zone 22
IEC60079-0:2007
IEC60079-15:2005
Gland Nut Torques:
EXP-0 range
ATEX Coding:
II 3 GD
13-15mm (Yellow - std.)
11-13mm (black)
9-11mm (white)
7-9mm (dark grey)
EXP-A range
3.16Nm (28 lb/in)
3.16Nm (28 lb/in)
3.16Nm (28 lb/in)
3.16Nm (28 lb/in)
ATEX Certificate No:
ATEX Classification:
Baseefa09ATEX0232X
Ex nA IIC T6 Gc
Ex tc IIIC T85˚C Dc
20-22mm (Yellow - std.)
18-20mm (black)
16-18mm (white)
14-16mm (dark grey)
3.16Nm (28 lb/in)
3.16Nm (28 lb/in)
3.16Nm (28 lb/in)
3.16Nm (28 lb/in)
Materials:
Body Mouldings:
Flammability Rating:
UV Resistance:
Contacts:
Polyester
Tightening Torques:
Panel mount nut
Flange & Bulkhead
fixing screws
UL94V-0
2.25 Nm
0.9 Nm
To EN50021:1999
Machined Solid Brass, Nickel plated
O Rings:
Nitrile
Panel Sealing Gasket:
Silicone Rubber
Compliant
Dimensions:
Overall dimensions of connectors when mated together
EXP-0911 + EXP-0921
EXP-A911 + EXP-A921
230 mm max.
270 mm max.
CONTACT LAYOUT
EXP-0911 + EXP-0931
EXP-A911 + EXP-A931
135 mm max. (to panel)
175 mm max. (to panel)
EXP-0911 + EXP-0941
EXP-A911 + EXP-A941
145 mm max. (to panel, mid point on flange)
174 mm max. (to panel, mid point on flange)
2 pole
5 pole
3 pole
7 pole
4 pole
10 pole
www.bulgin.co.uk