LPE-TS Series 24V DC-AC Inverter
400 VA
Features
•
The LPE Series of DC-AC Inverters pro-
vides one of the cleanest, and most reli-
able AC power available on the market.
The LPE-TS further increases your sys-
tem’s “up-time” by including an built-in
transfer switch to transfer your load to
mains power should inverter power be
lost due to loss of DC Input, Over Tem-
perature, or a myriad of other situations.
The LPE-TS provides the dependable AC
power you need in very harsh environ-
ments.
Specifications
Input Voltage:
24 Vdc (19-30 Vdc)
ETS300 132-2, 4.7.1
120 VAC
60 Hz
400VA
Inrush Current:
Output Voltage:
Output Frequency:
Max Output Power:
Output Regulation:
Crest Factor:
•
The mechanical design allows the in-
verter to be mounted on any flat surface
such as a cabinet door, a side-wall, a
filler panel, or wherever your equipment
and imagination allow. The standard
connections mean you bolt it on, plug it
in, and you’re ready to go.
Less than 2.0%
Maximum 2.8:1
Total Harmonic Distortion: <1.0%
Efficiency:
DC Noise Injection:
86% Typical
dBRNC <30
Protection: Input & Output Fuse Protected, Input Undervoltage, Input
Overvoltage, Output Overload, Output Short Circuit, Over temperature
FRONT PANEL INDICATORS AND ALARMS
•
The LPE-TS is the answer for the in-
creased demand for critical ancillary AC
equipment running in DC powered cabi-
nets or near other uninterruptible DC
sources. In these applications it allows
quick and easy access to uninterruptible
AC Power and AC mains for maximum
availability.
Green LED:
Input Good
Bi-Color Red/Green LED: Summary Fault / Output Good
ENVIRONMENTAL
Cooling: Internal, Variable speed fan (front to rear airflow)
Operating Temperature: -20°C to +55°C
Storage Temperature:
Humidity:
AGENCY COMPLIANCE
-40°C to +65°C
0-95%, non-condensing
Safety: UL60950-1, CE Marked to LVD (EN60950-1)
Input EMI: EN300 386:2000 (EN55022:1998 Class A)
Output EMI: EN55022 Class A
MECHANICAL
Dimensions:
11.7 x 7.1 x 1.5 (297mm x 180mm x 38mm)
Weight:
3 lbs. (1.36kg)
DC Input Connection:
2 position terminal block
AC Output Connection: 3 x IEC C-13 receptacles
Ground Connection:
Transfer Time:
8-32 threaded stud
50 mSec to AC mains
Ordering Information
Part no.
LPE400-24-120-TS
Description
400 VA Inverter, 24 Vdc Input, 120 VAC, 60 Hz, Output, Auto Transfer Switch
DEMANDING APPLICATIONS DEMAND TDIPOWER
www.tdipower.com
© Copyright 2008, Transistor Devices, Inc. 17481A