500-4000 Watts  
HELIOSTM  
MiniSystem 3500  
3500W 48VDC Compact Power Solution  
Electrical Specs  
Input  
AC Input  
Voltage Range  
110/120VAC (86 - 132 VAC)  
(250 watt rectifiers)  
208/240VAC (176 - 264VAC)  
(500 watt rectifiers)  
Frequency  
Efficiency  
50 - 60 Hz (45 - 65 Hz)  
>86% @ full load  
Power Factor  
0.99 (50 - 100% output load)  
Total  
Harmonic Distortion  
<5% @ loads over 50% of rated current  
Output  
DC Output  
Voltage Range  
-54.5 VDC  
(user selectable -48 to -55.5VDC)  
Special Features  
Maximum  
Output Power  
3500 W Constant Power Output System  
Available in 110VAC or 220VAC systems  
110 VAC systems can be configured with two to eight,  
250W Output Rectifiers providing up to 1750W with  
N+1 Redundancy  
220 VAC systems can be configured with two to eight,  
500 W Output Rectifiers providing up to 3500W with  
N+1 Redundancy  
1750 watt/system @110VAC  
(250 watt rectifiers) with N+1  
3500 watt/system @ 220VAC  
(500 watt rectifiers) with N+1  
Voltage Regulation  
Dynamic Response  
+/- 0.5% load/line and +/- 1.0%  
load/line/temperature  
from +/-5% for 10% to 90% or 90% to 10%  
load step changes  
Adjustable DC Output Voltage: (-48 to -55.5V)  
Adjustable Temperature Compensation slope  
Adjustable Low Voltage Disconnect threshold  
Adjustable Battery Charge Control (2A to 20A)  
Distribution: 10 Fuse Positions (0 to 10A each) - Up to  
five breakers  
Power Factor Correction  
Current Sharing  
Soft Switching Technology  
Full Output Power at Full Temperature Range  
Full Complement of LED and Output Alarms Available  
Connections for up to Two Battery Strings  
EMI Filter Included  
Compact Dimensions (21.5"W x 5.25"H x 14"D) (550 x  
133 x 300mm)  
Protection and/or  
Disconnect  
fuses/breakers  
Parallel Operation  
+/- 10% of rated current between rectifiers  
Power/Current Limit  
102.5% +/- 2.5% of rated power at output  
voltages >42VDC  
Capacitor Precharge  
Hold-up Time  
Automatic upon insertion  
Output voltage remains above -42V  
for 30 msec  
Voice Frequency Noise  
High Frequency Noise  
<55 dB rnC  
<250 mV rms  
Environmental  
Fan shelf (220 V rectifier shelf) for increased  
temperature range, and installation in areas with low  
volume or no air flow  
EMC/EMI: FCC Class B, CISPR Class A for digital devices,  
Bellcore GR-1089-CORE  
ESD: Bellcore TR-NWT-001089  
Temperature: -40° to +50°C with natural convection cooling (250 W  
rectifiers), -40°C to +65°C with forced air cooling (500 W rectifiers) @ 250  
cfm  
Safety  
Humidity: 0 to 95% RH (non-condensing)  
Acoustic Noise: <65dB for full system including eight rectifiers, fan unit  
Cooling: natural convection / forced air  
UL 1950  
UL1801  
CSA C22.2 No. 950  
IEC-950  
Shock and Vibration: Bellcore TR-NWT-000063  
Fire Resistance: UL94VO  
Voltage Surge Protection: meets IEEE C62.41-1991  
172  
America’s (USA): 1-888-41-ASTEC  
Europe (UK): 44 (1384) 842-211  
Asia (HK): 852-2437-9662  
rev 12.01.01