AVO200
ELECTRICAL SPECIFICATIONS
Input
Input voltage
36 - 75 Vdc
Input Surge
Efficiency
100 V / 100 mSec
12 V at 100% load is 94%
5 V at 100% load is 94.5%
I/O insulation
I/O isolation
Basic insulation
2250 Vdc
Output
Output Voltage
12 V nominal
5 V nominal
Output current maximum
Noise & ripple
16.7 A for 12 V version
40 A for 5 V version
12 V is 70 mV pk-pk max
5 V is 120 mV pk-pk max
Over Temperature protection
-Baseplate
-Open frame
110 °C baseplate
120 °C hot-spot
Over voltage protection Method / OVP operation
Auto restart /130% Vout
Hiccup / 150% Iout
Over current protection Method / OCP operation
Control
Enable
TTL compatible (negative logic)
80% to 110% Vout
Trim function
Remote sense
Switching Frequency
Sense connections proivided
150 Khz
ORDERING INFORMATION
Model number
AVO200-48S05B-6L
AVO200-48S05-6L
AVO200-48S05PB-6L
AVO200-48S12B-4L
AVO200-48S12B-6L
AVO200-48S12-6L
Input voltage
36-75 Vdc
36-75 Vdc
36-75 Vdc
36-75 Vdc
36-75 Vdc
36-75 Vdc
Output voltage set point
5 V / 40 A
Output current
40 A
Efficiency
94.5%
5 V / 40 A
40 A
94.5%
5 V / 40 A
40 A
94.5%
12 V / 17 A
16.7 A
94.0%
12 V / 17 A
16.7 A
94.0%
12 V / 17 A
16.7 A
94.0%
Default = Negative remote control
P
B
= Positive remote control
= Baseplate
-6 = 3.8 mm pin length
-4 = 4.8 mm pin length
2
advancedenergy.com