Power Line Filters
Three Phase
High Performance
13-PDB Series
Features
I
I
I
I
I
I
I
Excellent attenuation for high voltage impulse
Metal case provides effective EMI shielding
Epoxy molded for internal component reliability
Excellent filtering characteristics for both normal
and common mode
Various current ratings available: from 5 to 200 Amps
Operating temperature: -40°C to +85°C
Designed for 3-phase, 3-line connection systems
Digital equipment
Industrial equipment (UPS, inverters and converters)
Circuit Diagram
Circuit 1
A
B
C
A'
B'
C'
Applications
I
I
G
Circuit 2
A
B
C
A'
B'
C'
G
Specifications
Model
13-PDB-005-12-A
13-PDB-010-12-A
13-PDB-020-12-B
13-PDB-035-12-B
13-PDB-050-12-B
13-PDB-080-13-C
13-PDB-100-14-C
13-PDB-150-14-C
13-PDB-200-14-D
Rated Voltage
(@ 50/60Hz)
Rated
Current
5A
10A
20A
35A
50A
80A
100A
150A
200A
Leakage
Current (Max.)
Circuit
Diagram
Temperature Rise
(Max.)
4.5mA
1
9.0mA
30°C
480/277VAC
20mA
2
Note: Test Voltage 2250VDC one minute, line to ground.
Insulation Resistance: 500MΩ.
API TECHNOLOGIES
• 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH
• Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF88