V-EA INTERNAL RESISTANCE  
Resistances listed are “hot” values, as  
opposed to cold start values. Operating  
voltage drop across the V-EA and power  
loss per pole can be approximated with  
basic formulas:  
Trip Characteristic  
Rated  
Current  
(Amp)  
B
C
D
E
G
Z
(Ohms)  
(Ohms)  
(Ohms)  
(Ohms)  
(Ohms)  
(Ohms)  
0.3  
0.5  
0.75/0.8  
1.0  
1.6  
2.0  
2.5  
3.0  
3.5  
4.0  
5.0  
6.0  
8.0  
10  
12/12.5  
13  
15/16  
20  
25  
0.0528  
0.0216  
0.0113  
0.0085  
0.0067  
0.0050  
0.0032  
0.0025  
0.0019  
0.0018  
16.8620  
6.8540  
3.0540  
1.7000  
0.5870  
0.4190  
0.2950  
0.2020  
0.1390  
0.1090  
0.0654  
0.0528  
0.0278  
0.0216  
0.0084  
0.0085  
0.0067  
0.0050  
0.0032  
0.0025  
0.0019  
0.0018  
16.8620  
6.0009  
3.0540  
1.7560  
0.5870  
0.4190  
0.2950  
0.2020  
0.1390  
0.1090  
0.0654  
0.0491  
0.0240  
0.0187  
0.0085  
0.0076  
0.0064  
0.0041  
0.0027  
0.0022  
0.0018  
0.0017  
14.52000  
5.92000  
2.70000  
1.48000  
0.57400  
0.40500  
0.26900  
0.18600  
0.13900  
0.10600  
0.05900  
0.04600  
0.03040  
0.02020  
0.00724  
0.00724  
0.00731  
0.00582  
0.00411  
0.00272  
0.00212  
0.00184  
0.00172  
16.8620  
6.8540  
3.0540  
1.7560  
0.5870  
0.4190  
0.2950  
0.2020  
0.1390  
0.1090  
0.0654  
0.0491  
0.0333  
0.0211  
0.0084  
0.0084  
0.0076  
0.0064  
0.0046  
0.0030  
0.0022  
0.0019  
0.00179  
31.5060  
10.2460  
5.3920  
2.6910  
0.9440  
0.8900  
0.4290  
0.3460  
0.1790  
0.1620  
0.1050  
0.0823  
0.0371  
0.0278  
0.0151  
0.0151  
0.0114  
0.0075  
0.0050  
0.0032  
V
P
= I  
= I  
x R  
x R  
DROP  
OPERATING  
TABLE  
TABLE  
2
LOSS P/P  
OPERATING  
Voltage drops should be reviewed when  
V-EAs with high internal resistance are  
used (e.g., load voltage minimums).  
Power loss should be reviewed when  
V-EAs with high rated currents are used  
(e.g., enclosure heating).  
The listed V-EA internal resistance values  
should not be used in calculations of  
available short-circuit current downstream  
of the V-EA. The dynamic impedance of  
the V-EA under short-circuit conditions  
can vary significantly from internal  
resistance values in normal operation.  
30/32  
40  
50  
60/63  
LINE CURRENT FREQUENCY EFFECTS ON TRIP CURVES  
The thermal trip is not affected by the frequency of the line  
current. The magnetic trip is within the trip zone of the  
characteristic curve for frequencies from 16 2/3 to 60Hz. At  
lower and higher frequencies, the magnetic trip will be delayed  
longer than indicated by the characteristic curve, roughly as  
follows:  
Frequency Effects on Magnetic Trip Curves  
Trip  
Curve  
Trip Zone  
At  
Trip Zone  
At  
Trip Zone  
At  
Trip Zone  
At  
Trip Zone  
At  
16 2/3 - 60Hz  
(x RC)  
100 Hz  
(x RC)  
200 Hz  
(x RC)  
400 Hz  
(x RC)  
DC  
(x RC)  
Z
B
C
G
D
E
2 - 3  
3 - 5  
2.2 - 3.3  
3.3 - 5.5  
2.4 - 3.6  
3.6 - 6.0  
2.8 - 4.2  
4.2 - 7.0  
3.0 - 4.5  
4.5 - 7.5  
At 100Hz: Mag. Trip Current = 1.1 x curve current  
At 200Hz: Mag. Trip Current = 1.2 x curve current  
At 400Hz: Mag. Trip Current = 1.4 x curve current  
5 - 10  
8 - 10  
10 - 16  
14 - 18  
5.5 - 11.0  
8.8 - 11.0  
11.0 - 17.6  
15.4 - 19.8  
6.0 - 12  
7.0 - 14.0  
11.2 - 14.0  
14.0 - 22.4  
19.6 - 25.2  
7.5 - 15.0  
12.0 - 15.0  
15.0 - 24.0  
21.0 - 27.0  
9.6 - 12.0  
12.0 - 19.2  
16.8 - 21.6  
At DC:  
Mag. Trip Current = 1.5 x curve current  
For example, at 16 2/3 - 60 Hz the magnetic trip zone for the “G”  
characteristic is 8 to 10 times the rated current of the specific  
V-EA (i.e., hold for at least 100ms at 8 x RC, trip in less than  
100ms at 10 x RC). With a 400Hz current, a magnetic trip at 10  
x RC would be greatly delayed (thermal would likely trip first), as  
the magnetic trip zone is now 11.2 to 14 x RC. If a quicker  
magnetic trip is required with 400Hz, the “B” or “C” characteristic  
should be considered.  
MECHANICAL ENDURANCE RATINGS (ON/OFF OPERATIONS)  
Application  
2 x (1.15 x RC)  
2 x RC  
RC  
No Load  
Total  
AC General Use  
1000  
6000  
5000  
6000  
4000  
4000  
4000  
4000  
4000  
10000  
10000  
10000  
10000  
10000  
AC Motor Starting Across the Line  
AC Incandescent Lamps (Tungsten)  
AC Electrical Discharge Lamps (Ballast)  
AC Resistance  
6000  
6000  
Manufacturers self certification  
20000 ON/OFF operations with no load  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  