UL 489
R-Series
UL1077 Recognized
Supplementary
Protector
DIN Rail Mounted
17.5mm width per pole
Thermal Magnetic
480Y/277V AC, 50/60Hz
10kA Short Circuit
Withstand Capacity
•
Positive Trip indicator
(Green - off/tripped, Red - on)
•
Applications (on the load side
of Branch Circuit Protection)
include: Sensitive Electronics,
Power Supplies, Appliance
circuits, etc.
E301611
Voltage Rating
•
•
•
•
•
UL 1077
UL 508
480Y/277VAC
0.5-6A (RC): 10kA with no back-up fuse
8-63A (RC): 10kA with UL-listed
Class J back-up fuse; 5kA with no back-up fuse
0.5-63A (RC): 10kA
30°C (86°F)
-25° to 60°C (-13° to 140°F)
-25° to 75°C (-13° to 167°F)
14-3 AWG: 17.5 lb-in. (2.0 Nm)
18-16 AWG: 25 lb-in. (2.8 Nm)
IP20 at front
6,000 cycles on/off
10,000 cycles on/off
copper wire only 60/75°C
3g (18-50Hz)
In any plane
UL 1077
Equipment Breakers
Short Circuit Withstand Rating
(UL - Ratings)
Interrupting Capacity
(IEC/EN60898/60947-2)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
and Torque
Terminal Protection Degree
Electrical Life
Indicator
window
ON
OFF
Trip curve
and amperage
window display.
Earth Leakage
Circuit Breakers
Mechanical Life
Wire Connection
Vibration Resistance
Mounting Orientation
short CirCuit WithstanD ratinGs for r-series suppleMentary proteCtor
Backup Protection
Trip
Curve
All
Amp
Range
0.5 - 6A
8 - 63A
UL-Listed
Class J Fuse
up to 10kA
4xRC*
4xRC*
No Backup Fuse
Required
up to:
10kA
5kA
ANNEX
All
*up to nearest rated current
DC voltage rating: 48 VDC (self-certified).
62
Altech Corp.
®
• 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com