1397
Digital DC Drive
1397 Product Selection
The 1397 product program includes standard 1397 DC drives rated
from (1.1-448 kW) 1.5-600Hp, offered in both regenerative and non-
regenerative configurations. All drives are supplied chassis mounted –
IP 00 (open) – for user installation. There is a limited offering of
factory mounted options along with a larger offering of option kits for
user installation. All standard products in this program are predefined
and not generally subject to modification. For special requirements
consult Allen-Bradley.
230V AC Input Product Selection
1397
Bulletin Number
- A001N
➊
- HA2
➋
-
Rating Type
(must be specified)
Control Interface
(must be specified)
DS050
AC Line Disconnect
(optional)
-
PE
Pulse Encoder Interface
(optional)
Nominal
Drive Rating 230V AC Drives — IP 00 (Open) — No Enclosure
kW (Hp)
➌
1.2 (1.5)
1.5 (2)
2.2 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
56 (75)
75 (100)
93 (125)
112 (150)
Code
A001__➊
A002__➊
A003__➊
A005__➊
A007__➊
A010__➊
A015__➊
A020__➊
A025__➊
A030__➊
A040__➊
A050__➊
A060__➊
A075__➊
A100__➊
A125__➊
A150__➊
230V AC Rated➍ 240VDC Rated➍
Line Amps
Armature Amps
10
11
13
19
26
33
48
63
80
94
125
154
186
226
307
370
443
7
9
12
20
29
38
55
73
93
110
146
180
218
265
360
434
521
150VDC Rated➎
Field Amps
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15
➊
Either an “N” (non-regenerative) or an “R” (regenerative) drive must be specified.
➋
At least one of either a Human Interface Module (HIM) or Option 1203-GD2 using
DriveTools32™
will be required to program the drive. Chosen option(s) may be ordered factory installed (if
available) or as user installed kits.
➌
kW ratings are based on rated input voltage.
➍
Consult factory for alternate voltages.
➎
For special field voltage requirements refer to the Enhanced Field Supply Option.