AD7416/AD7417/AD7418  
With a VDD = 3 V, for each 400 µs cycle, the AD7416 spends  
40 µs (or 10% of the time) in conversion mode. It spends 360 µs  
(or 90% of time) in partial power-down mode. Thus, the aver-  
age power dissipated by the AD7416/AD7417/AD7418 is  
The CONVST pin should not be pulsed when reading from or  
writing to the port.  
Figure 17 shows the recommended minimum times for the  
CONVST pulse when the temperature channel is selected.  
Figure 18 shows the minimum times an analog input channel  
is selected.  
3 mW × 0.1+1mW × 0.9 = 1.2 mW  
Mode 2  
For applications where temperature measurements are required at  
a slower rate, e.g., every second, power consumption of the part  
can be reduced by writing to the part to go to a full power-down  
between reads. The current consumption in full power-down is  
typically 0.2 µA and full power-down is initiated when D0 = 1  
in the Configuration Register. When a measurement is required,  
a write operation can be performed to power-up the part. The  
part then performs a conversion and is returned to power-down.  
The temperature value can be read in the full power-down  
because the I2C bus is continuously active.  
APPLICATIONS INFORMATION  
SUPPLY DECOUPLING  
The AD7416/AD7417/AD7418 should be decoupled with a  
0.1 µF ceramic capacitor between VDD and GND. This is  
particularly important if the part is mounted remote from the  
power supply.  
POWER-ON-RESET  
To ensure proper power-on-reset, make sure that the supply  
voltage on the VDD pin is at 0 V. Refer to application note  
AN-588 for more information. A failed power-on-reset can  
prevent the default values from being loaded into the AD7416/  
AD7417/AD7418 registers. If the correct values are not loaded  
into the registers, then the device will not start operating. The  
output from the value registers will be a constant value.  
The power dissipation in this mode depends on the rate at which  
reads take place. Taking the requirements for a temperature  
measurement every 100 ms as an example, the optimum power  
dissipation is achieved by placing the part in full power-down,  
waking it up every 100 ms, letting it operate for 400 µs and  
putting it into full power-down again. In this case, the average  
power consumption is calculated as follows. The part spends  
40 µs (or 0.04% of time) converting with 3 mW dissipation and  
a 99.96 ms (99.96% of time) in full shutdown with 60 nW dissipa-  
tion. Thus, the average power dissipation is  
To get the device operating again, the registers will have to be  
loaded with their default values via the I2C bus. Therefore, in  
the event of an inadequate power-on-reset and for all three  
devices, the following registers should be loaded with their  
default values:  
3 mW × 0.004 + 60 nW × 0.9996 = 1.2 µW  
Configuration Register 1Default Value = 00h  
Configuration Register 2Default Value = 00h  
The fastest throughput rate at which the AD7416/AD7417/  
AD7418 can be operated is 2.5 kHz (i.e., a read every 400 µs  
conversion period). Since TOTI and THYST are 2-byte reads, the  
read time with the I2C operating at 100 kbit/s would be 270 µs.  
If temperature reads are called too often, reads will overlap  
with conversions, aborting them continuously, which results in  
invalid readings.  
T
HYST Setpoint RegisterDefault Value = 4B00h  
TOTI Setpoint RegisterDefault Value = 5500h  
MOUNTING THE AD7416  
The AD7416/AD7417/AD7418 can be used for surface or air  
temperature sensing applications. If the device is cemented to a  
surface with thermally conductive adhesive, the die temperature  
will be within about 0.2°C of the surface temperature, thanks to  
the devices low power consumption. Care should be taken to  
insulate the back and leads of the device from the air, if the  
ambient air temperature is different from the surface tempera-  
ture being measured.  
CONVERT START MODE  
The AD7417/AD7418 has an extra mode, set by writing to the  
MSB of the Config2 Register.  
CONVST Pin Mode  
By setting the CONVST Mode Bit to 1, conversions are initiated  
only by using the CONVST pin. In this method of operation,  
CONVST is normally low.  
The ground pin provides the best thermal path to the die, so the  
temperature of the die will be close to that of the printed circuit  
ground track. Care should be taken to ensure that this is in good  
thermal contact with the surface being measured.  
The rising edge of CONVST starts the power-up time. This  
power-up time is 4 µs. If the CONVST high time is longer than  
4 µs, a conversion is initiated on the falling edge of CONVST  
and the track-and-hold also enters its hold mode at this time. If  
the CONVST high time is less than 4 µs, an internal timer,  
initiated by the rising edge of CONVST holds off the track-and-  
hold and the initiation of conversion until the timer times out  
(4 µs after the rising edge of CONVST, which corresponds with  
the power-up time). CONVST input remains low at the end of  
conversion, thus causing the part to enter its power-down mode.  
In this method of operation, CONVST is normally low with a  
high going pulse controlling the power-up and conversion starts.  
As with any IC, the AD7416/AD7417/AD7418 and its associ-  
ated wiring and circuits must be kept free from moisture to  
prevent leakage and corrosion, particularly in cold conditions  
where condensation is more likely to occur. Water resistant  
varnishes and conformal coatings can be used for protection.  
The small size of the AD7416 package allows it to be mounted  
inside sealed metal probes that provide a safe environment for  
the device.  