5B47
Output, 100 kHz Bandwidth
Bandwidth, -3 dB
500 µV rms
4 Hz
Output Rise Time, 10% to 90% Span
200 ms
Common-Mode Voltage (CMV)
Input-to-Output, Continuous
Output-to-Power, Continuous4
Transient
1500 V rms, maximum
±3 V, maximum
ANSI/IEEE C37.90.1-1989
Common Mode Rejection (CMR)
160 dB
60 dB
1 k Ω Source Imbalance, 50/60 Hz
Normal Mode Rejection (NMR), 50/60 Hz
Input Protection
Continuous
240 V rms, maximum
Transient
ANSI/IEEE C37.90.1-1989
Output Resistance
50 Ω
Voltage Output Protection
Output Selection Time
Continuous Short to Ground
6 µs @ Cload = 0 to 2,000 pF
Output Enable Control
Max Logic "0"
+1 V
Min Logic "1"
+2.5 V
Max Logic "1"
+36 V
Input Current "0"
0.4 mA
Open Input Response
Open Input Response Time
Power Supply Voltage
Power Supply Current
Power Supply Sensitivity, RTI
Mechanical Dimensions
Upscale
10 seconds
+5 V ±5%
30 mA
±2 µV/% of Vs
2.275" x 2.375" x 0.595"
(57.8 mm x 59.1 mm x 15.1 mm)
Environmental
Temperature Range
Rated Performance
Operating
-25°C to +85°C
-40°C to +85°C
Storage
-40°C to +85°C
Relative Humidity
RFI Susceptibility
0 to 93% @ +40°C non-condensing
±0.5% Span error @ 400 MHz, 5 Watt, 3 ft
Includes the combined effects of repeatability, hysteresis, and nonlinearity and assumes RL > 50 k Ω. Loads heavier than 50 k Ω will degrade nonlinearity and gain temperature
coefficient.
2±1 µV/°C is equivalent to 0.02°C/°C for Type J thermocouples; 0.025°C/°C for Type K and T thermocouples; 0.016°C/°C for Type E thermocouples; 0.168°C/°C for Type R and S
thermocouples.
3When used with the model AC1361 CJC sensor (see Accessories section), which is provided on each channel of 5B Series backplanes and mounting cards.
4The output common must be kept within ±3 V of power common.
Specifications subject to change without notice.