欢迎访问ic37.com |
会员登录 免费注册
发布采购

5B02 参数 Datasheet PDF下载

5B02图片预览
型号: 5B02
PDF下载: 下载PDF文件 查看货源
内容描述: 5B系列16通道背板 [5B Series 16 Channel Backplane]
分类和应用:
文件页数/大小: 7 页 / 183 K
品牌: ADI [ ADI ]
 浏览型号5B02的Datasheet PDF文件第1页浏览型号5B02的Datasheet PDF文件第3页浏览型号5B02的Datasheet PDF文件第4页浏览型号5B02的Datasheet PDF文件第5页浏览型号5B02的Datasheet PDF文件第6页浏览型号5B02的Datasheet PDF文件第7页  
5B02  
GENERAL DESCRIPTION  
connects +5 VDC power common to input/output common  
Model 5B02 Backplane - The 5B02 diagrammed in Figure 1, is  
a 16 channel backplane. It incorporates input and output buses  
that take advantage of the internal series output switches in the  
input modules and the track-and-hold in the output module.  
Designers integrating the 5B02 into a measurement and control  
system do not need external multiplexers and can use a single  
digital-to-analog converter to server numerous output channels.  
Digital outputs from the host data acquisition system are used  
to address the 5B Series modules and designate inputs and  
outputs. Only one analog input, one analog output, and a  
number of digital outputs are required to address up to 64  
analog input/output channels.  
(backplane measurement ground). A connection between  
power common and input/output common is important for the  
5B Series modules to function properly; however, if this  
connection is made elsewhere in your system (the best place is  
usually near the A/D or D/A converters), W4 should be cut  
since a ground loop could result.  
Model 5B02 Address Selection Jumpers – The 5B02 backplane  
can hold 16 modules in any combination of inputs or outputs.  
Address decoders on the backplane (separate decoders are  
provided for inputs and outputs) determine which module is  
read (inputs) or driven (outputs). To permit system expansion,  
up to four backplanes can be daisy-chained on the system I/O  
ribbon cable for a total of 64 channels. Jumpers on each  
backplane (labeled SH1-5 and SH6-10) determine the block of  
16 addresses assigned to each backplane. Input (read) and  
output (write) addressing are completely independent; in all  
cases, Jumpers 1-5 control inputs and 6-10 control outputs.  
Independent addressing might be used, for example, to update  
output modules without interrupting the monitoring of input  
modules.  
Model 5B02 System Connectors – Signal connections between  
the 5B02 backplane and the associated measurement or control  
system are made at P1. One signal path is provided for inputs  
and one for outputs. Input and output modules are  
independently addressed by two sets of six address pins and an  
enable pin. In addition, a number of grounded pins are present  
in the connector pin-out to provide shield conductors in the  
ribbon cable. In some cases, discussed below, the ground  
conductors will not provide an accurate signal reference, so a  
SENSE pin is also provided in the pin-out. Several jumper and  
component options in the backplane provide optimum ground  
connections for various circumstances.  
Backplanes are factory configured with jumpers at Positions 1  
and 6. This sets up the backplane as a stand-alone 16 –channel  
system; the two highest order address bits in the read and write  
addresses are ignored. Moving the jumpers to any other  
position in the two blocks enables decoding of the full six  
address bits. The exact position of the jumper determines  
address position for the backplane. To use multiple backplanes  
in this manner, connect the corresponding I/O connector pins  
of each backplane in parallel. CAB-01 is a ribbon cable with  
three 28-pin connectors designed for this purpose.  
Model 5B02 Grounding – Each 5B02 backplane is factory  
configured with Jumpers W1, W2, and W4 installed. Jumper W1  
grounds the shield wires in the ribbon cable (Pins 2,5, and 6) at  
the 5B02 backplane. This will usually be the primary ground  
connection between the 5B02 and the measurement system.  
This connection is required if output modules will be used on  
the backplane. It is also required if there is no high impedance  
sense input (input low of a differential or pseudo-differential  
system) available on the measurement system. Jumper W2  
connects the sense input, if available, to Pin 25 so that the 5B02s  
ground is read. It can be left in place at all times. Jumper W4  
Figure 2  
Rev. 0 | Page 2 of 7