3B47  
GENERAL DESCRIPTION  
CUSTOM). Zero suppression can exceed 100% of the input  
The 3B47 is a single-channel isolated thermocouple signal-  
conditioning module which interfaces, amplifies, isolates,  
protects, linearizes and filters analog input voltages from a J, K,  
T, E, R, S or B-type thermocouple. The thermocouple input  
signal is internally linearized to provide an output voltage which  
is linear with temperature, High accuracy internal cold junction  
compensation and a predictable upscale open circuit indication  
provide a complete signal conditioning solution. To accurately  
measure low level signals in electrically noisy environments,  
+1500 V peak of galvanic transformer-based isolation with a  
common mode rejection (CMR) of 160 dB @ 50/60 Hz and a  
normal mode rejection (NMR) of 60 dB @ 50/60 Hz are  
provided. This plug-in, mix-and-match, hot-swappable module  
is easily field calibrated via front-panel zero and span  
adjustments.  
range. This enables suppression of a zero-scale input value  
many times larger than the total span for precise expanded-  
scale measurements of a selection portion of an input signal.  
The differential input circuit on the field side is fully floating,  
eliminating the need for any input grounding. Signal isolation  
by transformer coupling uses a proprietary modulation  
technique for linear, stable and reliable performance. A  
demodulator on the computer side of the signal transformer  
recovers the original signal which is then filtered and buffered  
to provide a low-noise, low-impedance output voltage.  
Internal cold-junction compensation largely corrects errors  
arising from parasitic thermocouples formed by thermocouple  
connection to the input screw terminals, providing an accuracy  
of +0.5oC over the +5oC to +45oC ambient temperature range.  
The module generates a predictable upscale signal to indicate an  
open thermocouple; for a downscale response, connect a 47  
M, 0.25 Watt resistor across screw terminals 2 and 4 on the 3B  
Series backplane.  
A chopper-stabilized low-drift input amplifier assures stable  
long-term stability. At the amplifier input, a zero-scale input  
voltage is subtracted from the input signal to set the zero-scale  
value. For user convenience, the zero and span optionally can be  
factory configured to meet custom needs (Model 3B37-  
.
.
Figure 2  
Rev. 0 | Page 2 of 8