 浏览型号DCM10048S12的Datasheet PDF文件第2页  
60-100 Watts  
DCM Series  
xppower.com  
Open Frame Telecom DC-DC Converter  
-48 VDC Input  
ETSI Compliant  
NEBS Compliant  
Convection-cooled  
High Power Density in 2 Small Package Sizes  
Covered Versions Available  
Specification  
Input  
General  
Input Voltage Range  
• 48 VDC nominal (36 - 75 VDC).  
Can be configured as -48 VDC input  
Efficiency  
• 85% typical  
(6)  
Isolation Voltage  
• 1500 VDC Input to Output (basic  
insulation), 1000 VDC Input to Ground,  
500 VDC Output to Ground.  
Input Current  
• DCM60: 1.5 A typical, 2.5 A max,  
DCM100: 2.2 A typical. 3.5 A max.  
Input Reverse Voltage • Continuous protection with  
Switching Frequency  
Power Density  
• 70 kHz typical  
• DCM60: 6.30 W/In3  
Protection  
automatic recovery  
Input Transient  
• Compliant with ETSI EN300 132:2003  
DCM100: 7.40 W/In3  
Undervoltage Lockout • 32 - 35V DC  
Protection  
MTBF  
• DCM60: 740 kHrs per MIL-HDBK-217F  
DCM100: 540 kHrs per MIL-HDBK-217F  
Output  
Environmental  
Output Voltage  
• 12 V, see table  
• 10% via potentiometer  
Operating Temperature • 0 °C to +50 °C with full load, derate  
linearly to 50% load at 70 °C convection  
Output Voltage Trim  
Minimum Load  
cooled. 0°C to 60°C with full load, derate  
• 5% minimum load required to meet all  
specification parameters  
linearly to 75% load at 70 °C with force  
(6)  
cooling 5CFM minimum  
Line Regulation  
Load Regulation  
Setpoint Accuracy  
0.5% of nominal with input variation of  
36-75V DC  
(6)  
Cooling  
• Convection or forced cooled  
(see operating temperature)  
1% of nominal with load variation  
5-100%  
Operating Humidity  
Storage Temperature  
Storage Humidity  
Operating Altitude  
Shock  
• 0 to 95% RH non condensing.(1,3)  
(2,3)  
• -40 °C to +80 °C.  
1% of nominal with 48V DC input  
and 50% load  
• 0 to 95% RH non condensing.(2,3)  
• 3000m.(3)  
Turn-on Time  
• 1 s typical from application of DC input  
3 shocks in each axis (total 18 shocks)  
Transient Response  
• <4% deviation with a 50-75-50% load  
change at 1 A/µs. Output returns to within  
1% in less than 500 µs  
(1,4)  
30g 11ms (half sine).  
(1,5)  
Vibration  
2g, 10 - 500Hz 10 sweeps.  
Ripple & Noise  
• 1% max pk-pk 20MHz bandwidth,  
0.1 µF capacitor connected across  
measuring points  
EMC & Safety  
(6)  
Emissions  
• Compliant with EN61204-3 2000,  
EN55022 class A conducted & radiated(7) ,  
ETSI EN 300 132-2 2003, ETSI 300 386-1  
1994, NEBS GR-1089-CORE issue 4  
Overvoltage Protection • 115-135% of nominal,  
recycle input DC to reset  
Overcurrent Protection • 105-150% of max current  
EFT/Burst  
• Compliant with EN61000-4-4 level 1 Perf  
Criteria A, ETSI 300 386-1 1994  
Short Circuit Protection • Continuous protection, trip and restart  
(6)  
(hiccup mode) characteristic  
Surge  
• EN61000-4-5 level 1 Perf Criteria A,  
Temperature  
Coefficient  
• 0.02%/°C (after 20 minute warm up)  
Conducted Immunity  
• Compliant with EN61000-4-6 level 2 Perf  
Criteria A, ETSI 300 386-1 1994, NEBS  
GR-1089-Core issue 4  
Notes  
Narrow & Wide  
Band Noise  
• ETSI EN 300 132-2 2003  
1. Compliant with ETS 300 019-1-3 May 1992 + ammendment 1 June 1997 class 3.1.  
2. Compliant with ETS 300 019-1-1 Feb 1992 class 1.1, ETS 300 019-1-2 Feb 1992 class 2.2.  
3. Compliant with NEBS GR-63-Core issue 3.  
4. Compliant with EN60068-2-27.  
5. Compliant with EN60068-2-6.  
Safety Approvals  
• EN60950-1 2001 + A11 2004, UL60950-1  
(2003), CSA-C22.2 No. 60950-1-03,  
CB Report IEC60950-1:2001,  
6. For further product information, see longform datasheet.  
7. For -48VDC class B operation , see longform datasheet.  
(6)  
CE Marked to LVD